Temperature:
Operating Range: 4.4°C (40°F) to 37.8°C (100°F)
Humidity:
Operating range: 0-95% relative humidity, non-condensing
Audible Alarm:
85+ dB at 10’ @ 3.2±0.5 KHz pulsing alarm, with voice messages “Fire!
Feu!” NOTE: This is not a CO alarm, but it will receive and transmit a CO
alarm signal (with voice message “Warning! Carbon Monoxide. Monoxide
de carbone!”) from an interconnected CO or combination smoke/CO alarm.
Sensor:
Photoelectric
Mounting:
Wall or ceiling
Applications:
Primary Direct or Indirect and Supplementary
Light Output:
177 Candela minimum (on axis measurement)
The following diagrams show that the light intensity gradually decreases
as the viewing angle is increased. Use this information to determine the
best location for the strobe light.
2. Product Features and Specifications
CEILING
90° 90°
45° 45°
SOURCE
LIGHT
CEILING
90° 90°
45° 45°
SOURCE
LIGHT
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
(LIGHT INTENSITY) (IN DEGREES)
PERCENT ANGLE
25 90
25 85
30 80
30 75
35 70
35 65
40 60
45 55
55 50
75 30-45
90 5-25
100 0
(LIGHT INTENSITY) (IN DEGREES)
PERCENT ANGLE
90° 60 55 50 45 40 35 30
0
ZERO AXIS
WALL
FLOOR
5
10
15
20
25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde P4010ACLEDSCA and is the answer not in the manual?

Kidde P4010ACLEDSCA Specifications

General IconGeneral
BrandKidde
ModelP4010ACLEDSCA
CategorySmoke Alarm
LanguageEnglish