EasyManua.ls Logo

Kidde VM-1 - Page 30

Kidde VM-1
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1: Fire geometry and smoke movement in buildings
26 VM-1 Smoke Management Application Guide
Electrical power requirements
All electrical installations must meet the requirements of
NFPA 70, National Electrical Code, in addition to
building code requirements. Normal electrical power
serving air conditioning systems will generally have
sufficient reliability for nondedicated zoned smoke
control systems.
Standby power for dedicated smoke control systems and
their control systems should be adequate for the
expected duration of a fire event.
Programming functions
Regardless of the type of smoke control system
installed, the control and programming device functions
will fall into three general categories:
The operation of fans: turning ON or OFF
The operation of compartmenting components
(dampers, doors, louvers, walls, or windows): to
OPEN or CLOSE
The toggling of HVAC system components from their
normal, nonfire condition: AUTO or AUTO OFF
From the two control categories the monitoring or status
of smoke control equipment will also be needed or
required.
Verification of devices results in a confirmation of:
An ON (fan) or OPEN (dampers, etc.) condition
An OFF (fan) or CLOSED (dampers, etc.) condition
Control and monitoring functions will fall into one of the
categories shown in Table 1 for fans or compartmenting
devices. Monitoring will take the form of a control panel
LCD or annunciator LED. Table 1 provides a list of
control actions and the devices they monitor.
Table 1: Control and monitoring functions
Control action
Resulting control or LED status
AUTO OFF
Overrides normal HVAC Controls
Turn Fan OFF
Only when Fan is OFF
Turn Fan OFF
Only when Fan is ON
Turn Fan OFF
Fan is ON & OFF
Turn Fan ON
Only when Fan is OFF
Turn Fan ON
Only when Fan is ON
Turn Fan ON
When Fan is ON & OFF
Control action
Resulting control or LED status
Turn Fan ON & OFF
Only when Fan is OFF
Turn Fan ON & OFF
Only when Fan is ON
Turn Fan ON & OFF
Only when Fan is ON & OFF
CLOSE Damper*
When Damper is CLOSED
CLOSE Damper*
When Damper is OPEN
CLOSE Damper*
When Damper is OPEN & CLOSED
OPEN Damper*
When Damper is CLOSED
OPEN Damper*
When Damper is OPEN
OPEN Damper*
When Damper is OPEN & CLOSED
OPEN &
CLOSE Damper* Damper is CLOSED
OPEN & CLOSE Damper*
When Damper is OPEN
OPEN & CLOSE Damper*
When Damper is OPEN & CLOSED
AUTO ON
Returns HVAC to normal operation
* For this table, damper is used to denote any compartmenting device.
For each of the control actions in Table 1 the verification
of the result is displayed at a monitoring point. For
example, a controlling action to “Turn Fan ON or OFF”
with a monitoring requirement to verify “Only when Fan
is ON” results in the capability to turn the fan ON or OFF
when a fire is detected. In addition, verification when the
fan is turned on in response to a fire will occur, usually in
the form of an LED at the VM-1 smoke control panel.
Note: Typically for a nondedicated HVAC fan, when the
fan is in its normal or auto operating state, there will be
suppression of the LED monitor point.
Control and monitoring examples
For Figure 21 on page 27 both fans and dampers are
used for smoke control. There are two zones for the
multiple zone arrangement. In the example, there is a
supply and return vent for each area with dampers
located at each vent and the system is equipped with
mechanical exhaust.
The smoke control system designer has determined that
in the event of a fire, the smoke zone must be placed
under a negative pressure and adjacent zones must
have positive pressures to prevent smoke intrusion.

Other manuals for Kidde VM-1

Related product manuals