Chapter 7 List of Parameters
56
Function
code
Name
Descriptions
Unit
Factory setting
Modif.
Setting
range
A0.02
Main reference
frequency
selector
0:Digital setting
Keyboard UP/DN or terminal UP/DN
1:AI1
2:AI2
3:AI3
4:Set via DI terminal(PULSE)
5:Reserved
1
0
O
0~5
A0.03
Set the operating
frequency
indigital mode
A0.11~A0.10
0.01
Hz
50.00
O
0~30000
A0.04
Methods of
inputting
operating
commands
0:Panel control
1:Terminal control
2:Communication control
1
1
O
0~2
A0.05
Set running
direction
0:Forward 1:Reverse
1
0
O
0~1
A0.06
Acc time 1
0.0~6000.0
0.1S
2kw or
below:6.0s
30kw~45kw:
20.0s
45kw or
above:30.0s
O
0~60000
A0.07
Dec time 1
0.0~6000.0
0.1S
2kw or
below:6.0s
30kw~45kw:
20.0s
45kw or
above:30.0s
O
0~60000
A0.08
Max. output
frequency
upper limit of frequency A0.11~
300.00Hz
0.01
Hz
50.00
X
0~30000
A0.09
Max. output
Voltage
0~1140
1V
VFD’s rated
values
X
0~60000
A0.10
Upper limit of
frequency
A0.12~A0.09
0.01
Hz
50.00
O
0~30000
A0.11
Lower limit of
frequency
0.00~A0.11
0.01
Hz
0.00
O
0~30000
A0.12
Basic frequency
0.00~ Max. output frequency A0.08
0.01
Hz
50.00
O
0~30000