CPU
Q0.0
Q0.1
Q0.4
HP043
50K
50K
10K
HP070
50K
50K
/
2.1.5 Edge Interrupts
I0.0-I0.3 in CPU support edge interrupt function, it can execute interrupt by rising edge and
falling edge of input signal. By using this function, it can capture the rising edge and falling
edge of input signal quickly. For some input signal whose pulse width is less than the CPU
scan time, it can respond quickly.
2.1.6 Data Retentive and Data Backup
Data retentive means the data in RAM can retain after power failure.CPU provides a lithium
battery (Replaceable but un-rechargeable) for data retentive. When CPU loses power, the data
in the RAM will be maintained by the lithium battery, and the retentive ranges will be left
unchanged at next power on.Through [Hardware] configuration in KincoBuilder, user can
select the type of data retentive (Such as V,C area) and the range. The life of battery is 5 years
and the retaining duration is 3 years at normal temperature.
Data backup is that CPU provides an E
2
PROM to store data permanently. At power on, the
CPU will restore the data from E
2
PROM into RAM to execute.
Note: Because E
2
PROM has a writing limit of 1 million times, users should avoid to write
data into data backup area frequently.
There are 448 bytes in V area for data backup (VB3648--VB4095),the data in this area will
save in E2PROM automatically.HMI-PLC sets VB3648--VB3902 as data backup by default,if
user needs to use VB3903--VB4095 for data backup,it needs to configure in PLC hardware
configuration.The configuration interface is as following figure.