9 Hydraulic schemes
Scheme with a three-way thermostatic actuator to protect the return water temperature
1
: 1
boiler, 2 controller, 3 boiler temperature sensor, 4 outside (weather) temperature sensor, 5 room
thermostat, 6 boiler pump, 7 - three-way thermostatic valve (manually adjustable), 8 - throttle (poppet)
valve, 9 HUW pump, 10 - HUW temp. sensor, 11 HUW tank, 12 burner feeder (stoker), 13 burner
fan, 14 main fuel feeder.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Preset boiler temp.
75-80C
Boiler settings
Min. boiler temp.
65C
Service settings Boiler settings
Boiler inc. by HUW and Mixer
5-20C
Service settings CH and HUW settings
Boiler room thermostat
eSTER T1
Service settings Boiler settings
1
The presented hydraulic scheme does not replace central heating engineering design and may be used for
information purposes only!