29
12.8 Temperature sensors checking
Temperature sensors can be checked by
measuring their resistance in given
temperature. In case of big differences
between measured resistance value and
values in table below, the sensor should be
replaced with a new one.
12.9 Optical sensor connection
The optical sensor should be connected in
accordance with point 12.5, be sure to
observe the polarization of the (+) and (-)
sensor signals. Readings of data from optical
sensor is possible in the menu:
Information → Flame
12.10 Mixers room temperature
connection
Room thermostat, connected to module B,
after disconnecting contacts reduces preset
temperature of the value of reduction the
preset temperature of the mixer from the
thermostat. Parameter is in the menu:
Mixer settings 1-2 → Mixer room
temperature
Value of parameter should be chosen in such
a way that after activating room thermostat,
temperature in the room should decrease. In
case of room panel make sure that this
parameter Thermostat select. is correctly
chosen in the menu:
Service settings → Mixer settings 1-2
12.11 Connection of reserve boiler
The controller can control a reserve boiler
(gas- or oil-fired), eliminating the necessity
of enabling or disabling this boiler manually.
Connection to a reserve boiler, e.g. oil-fired
one, should only be made by a qualified
fitter, in accordance with the technical
documentation of this boiler. The reserve
boiler should be connected via
relay to terminals 30-31 additional B module.
An example of a reserve boiler connection scheme: 1 –
additional B module, 2 – reserve boiler (gas- or oil-), 3 –
relay 6 VDC.
Standard version of the controller is not
equipped with a relay.