Scheme with heat buffer
3
: 1 boiler, 2 controller, 3 - boiler temperature sensor, 4 - outside (weather)
temperature sensor, 5 boiler pump, 6 buffer, 7 lower buffer temperature sensor, 8 upper buffer
temperature sensor, 9 burner fan, 10 burner feeder (stoker), 11 circulation pump, 12 mixer pump,
13 mixer temperature sensor, 14 mixer valve actuator, 15 - thermostatic 3-way valve for return
protection, 16 additional B module, 17 room thermostat, 18 - throttle (poppet) valve, 19 - three-way
thermostatic valve (manually adjustable).
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Preset boiler temp.
80C
Boiler settings
Min. boiler temp.
75C
Service settings Boiler settings
CH activation temp.
55C
Service settings CH and HUW settings
Buffer support
ON
Service settings Buffer settings
Loading start temperature
50C
Service settings Buffer settings
Loading end temperature
75C
Service settings Buffer settings
Mixer 1 support
CH ON
Service settings Mixer 1 settings
Max. mixer 1 temp.
70C
Service settings Mixer 1 settings
Mixer 1 heating curve
0.8 1.4
Mixer 1 settings
Mixer 1 weather control
ON
Mixer 1 settings
Mixer 2 support
Floor on
Service settings Mixer 2 settings
Max. mixer 2 temp.
45C
Service settings Mixer 2 settings
Mixer 2 heating curve
0.3 0.8
Mixer 2 settings
Mixer 2 weather control
ON
Mixer 2 settings
Mixer 2 room thermostat *
eSTER T2
Service settings Mixer 2 settings
* when a standard room thermostat with ON-OFF contacts is connected instead of the (17) room
thermostat, select the option for the thermostat = Universal or, if the setting is hidden, do not
need to select any option for the thermostat.
3
The presented hydraulic scheme does not replace central heating engineering design and may be used for
information purposes only!