(8) Mount a stopper bolt, a seal washer and a hexagon nut on an end cover. Lubricate an O-ring and
assemble it with the end cover ( Fig.16 ). Mount the end cover on the housing opening with hexagon
headedbolts(Fig.17). ForreassemblyofTypeFASspringreturnactuators,thespringcartridgemustbe
mountedonthehousingopening,insteadoftheendcover.
Fig.16
Fig.17
(9)Adjusttheshaftrotatingangle(valveopeningrange),accordingtoSection14ofthismanual.
(10)Checktheleakageofairfromanactuatorwithsoapsolution,accordingtothefollowingprocedures:
① ApplytheoperatingpressuretoPort[O]andcheckifanyexternalairleakageisdetectedthroughthe
contactofthehousingwiththeendcover,thestopperboltandthesealwasherintheright-handside
(Fig.18).
② Apply the operating pressure to Port [S] and check if any external leakage detected through the
contactofthehousingwithanotherendcover,anotherstopperboltandanothersealwasherinthe
left-handside(Fig.18).
Fig.18
③ Covertheleakdetectingholebelowthesolenoidvalvemountingpadwithasoapfilm,andcheckifany
airleakage is detectedthereduringa travel of the piston. Don’t apply the soap film directly to the
opening,sincethesoapmaypenetrateinsidethehousingandcausemalfunctionofanactuator.
O-ring<45F>
Endcover<2A>
Hexagonnut<132A>
Hexagonnut<133>
Sealwasher<155A>
Hexagonheadedbolt<35>
Endcover/housingcontact
Stopperbolt/sealwasher
Leak detecting hole
Endcover/housingcontact
Stopperbolt/sealwasher
O
S