TP-7044 6/23 15
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the
negative () lead first when disconnecting the battery. Reconnect the negative ()
lead last when reconnecting the battery.
Sound Shield Equipped Models: For access to the generator set to perform regular maintenance, remove the sound shield
doors and roof.
Sound Shield Roof and Door Removal
1. Open the service doors by releasing the latches, if equipped, or by using a flat-head screwdriver to turn the 1/4-turn
fasteners. See Figure 5.
2. Lift up the roof by using a flat-head screwdriver to turn the 1/4-turn fasteners. See Figure 5.
3. Slide the roof towards the service side of the unit for removal.
4. Open the front, rear, and non-service side doors as needed.
1. Sound shield roof
2. 1/4-turn fastener
3. Service door
4. Latch
Figure 5 Sound Shield Door and Roof Removal, Typical
3
4
GM102977
1
2
2