TP-6805 8/1542 Section 4 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Genset Run Time
Engine Run Time Until
Maintenance
h Read Only 200.0
Genset Controller Date Format MM/DD/YYYY or
DD/MM/YYYY
MM/DD/
YYYY
Genset Controller Time Format 12 or 24 hr 12 Hr
Genset Date Time of Next
Maintenance
Read Only N/A
Maintenance Period In Days days Read Only 365
Maintenance Period Remaining s Read Only 31536000
Genset Controller Clock Time
Zone Offset
Read Only 1/1/01
12:00:00
AM
Genset Personality Profile
ECM Model DO NOT CHANGE No ECM N/A
Maximum Alternator Current A Read Only 920
Engine Number Of Flywheel
Teeth
Locked 1
Engine Warmed Up Temperature _C/F 77 -- 140 _C 90_C N/A
Engine Cooled Down
Temperature
_C/F Locked 79_C
Engine Crank Disconnect Speed RPM 300 --1000 750
Engine Idle Speed RPM DO NOT CHANGE 2700
Engine Run Speed RPM 1000 -- 3900 3600
Engine Coolant Temperature
Protectives Enabled
No effect N/A
Engine Coolant Temperature
Sensor
No effect. N/A
Engine High Coolant
Temperature Inhibit Delay
s No effect. N/A
Engine Low Coolant Temperature
Warning Delay
s No effect. N/A
Engine High Coolant
Temperature Warning Delay
s No effect. N/A
Engine Low Coolant Temperature
Shutdown Delay
s No effect. N/A
Engine High Coolant
Temperature Shutdown Delay
s No effect. N/A
Engine Low Coolant Temperature
Warning Limit
_C/F No effect. N/A
Engine High Coolant
Temperature Warning Limit
_C/F No effect. N/A
Engine High Coolant
Temperature Shutdown Limit
_C/F No effect. N/A
Engine Coolant Temperature
Deadband
_C/F No effect. N/A
* Read Only = Not adjustable
[ Notes indicate applicability to genset model and accessories. N/A = Not applicable to these generator s ets.
] See TT-1584 for more information about digital inputs and outputs.
w Load management device (LCM, load shed kit, or RXT with combined interface/ load management board)