136 TP-6694 9/20
12. Replace the cover on the controller connection box.
13. Check that the generator set is in the OFF mode.
14. Reconnect the generator set engine starting battery, negative (-) lead last.
15. Reconnect power to the battery charger, if equipped.
Figure 66 Dry Contact Kit Analog Input Connections P36
Program the inputs and outputs using SiteTech
Use a computer with Kohler SiteTech software to assign functions to digital and analog inputs and outputs. Each input and
output corresponds to a controller connection. Verify that the settings are appropriate for the connected sensor, switch, or
equipment. Do not change factory-set inputs and outputs without verifying the input and output connections.
Refer to Introduction-List of Related Materials for the SiteTech Software Operation Manual part no.
SiteTech input and output parameters C1 through C14 are designated for use on the optional 15-relay dry contact board. See
Figure 67.
Test Dry Contact Relays
Verify the dry contact relay function by using the following procedure when troubleshooting.
1. Remove the user-supplied device wiring from the relay dry contact terminals.
2. Test the relay operation by connecting an ohmmeter across the NO and C terminals on the relay terminal strip.
3. Use a jumper wire to ground the selected fault terminal on the controller connection terminal strip. The relay contacts
should close and the ohmmeter should display a low resistance reading (continuity).
4. Install the user-supplied device wiring on the relay dry contact output terminals
Optional 5 V Power
(50 mA max.)
Optional 5 V Power
(50 mA max.)
100 ohm min. or
50 mA max. current
0-5 Volt Ratiometric Sensor
0-5 Volt Analog Device
+/- 3 Volt Analog Device
TP-6694-6
P36
+5
VPx
VNx
GND
+5
VPx
VNx
GND
+5
VPx
VNx
GND
P36
P36
Analog
Device
Output
GND
GND
Analog
Device
+
-