Output Enable is always on and controlled
by the generator controller.
Forced Charge Cycle
Reset
This feature allows a user to manually trigger
a refresh cycle where the charger goes into
the bulk cycle and cycles through the
charger cycle.
These is a single trigger of the feature. The
value returns to inactive automatically once
the action is triggered.
Target bulk voltage setpoint
Charger Voltage
Absorption (V)
Target absorption voltage setpoint
Charger Voltage
Float (V)
Target float voltage setpoint
Charger Voltage
Equalize (V)
Target equalize voltage setpoint.
Note: The controller’s high battery voltage
warning voltage shall set 0.2 V higher
then this value to avoid nuisance high
battery warnings while charger
performs the equalize cycle.