Target absorption termination setpoint that
controls when the absorption cycle
completes. Loads on the battery controller,
meters, and accessories may prevent the
absorption from completing it cycle causing
an absorption timeout error. The
recommended value is 1 A above the
measure resting load on the battery with all
connected accessories active. Lower values
are acceptable but may result in nuisance
faults.
The battery terminal open circuit voltage at
which the charger will consider the battery is
in a depleted state and will enter the
recovery charge cycle and softly starts the
charging process.