20 TP-7077 3/19
Parameter Name
Battery Type
Range
Default Settings
Description
Default 12 V
60 – 360
240
Default 24 V
60 – 360
240
FLA 12 V
60 – 360
240
FLA 24 V
60 – 360
240
AGM 12 V
60 – 360
240
AGM 24 V
60 – 360
240
Gel 12 V
60 – 360
240
Gel 24 V
60 – 360
240
NiCad 12 V
60 – 600
240
Charger Maximum
Absorption Time
Threshold (Min.)
NiCad 24 V
60 – 600
240
The setting for the maximum amount of time
the battery attempts to complete the
absorption cycle. Inability to complete
absorption with properly adjusted absorption
parameters may indicate a battery with
reduced capacity.
Default 12 V
60 – 600
480
Default 24 V
60 – 600
480
FLA 12 V
60 – 600
480
FLA 24 V
60 – 600
480
AGM 12 V
60 – 600
480
AGM 24 V
60 – 600
480
Gel 12 V
60 – 600
480
Gel 24 V
60 – 600
480
NiCad 12 V
60 – 600
480
Charger Maximum
Bulk Time Threshold
(Min.)
NiCad 24 V
60 – 600
480
The setting for the maximum amount of time
the battery attempts to complete the bulk
cycle.
Default 12 V
0, 23 – 672
335
Default 24 V
0, 23 – 672
335
FLA 12 V
0, 23 – 672
335
FLA 24 V
0, 23 – 672
335
AGM 12 V
0, 23 – 672
335
AGM 24 V
0, 23 – 672
335
Gel 12 V
0, 23 – 672
335
Gel 24 V
0, 23 – 672
335
NiCad 12 V
0, 23 – 672
335
Charger Refresh
Charge Cycle Time
(Hr.)
NiCad 24 V
0, 23 – 672
335
The setting for the amount of time between
refreshing the battery by charging though or
completing a charge cycle.
Default 12 V
Not available
Not available
Default 24 V
Not available
Not available
FLA 12 V
60 – 480
360
FLA 24 V
60 – 480
360
AGM 12 V
Not available
Not available
AGM 24 V
Not available
Not available
Gel 12 V
Not available
Not available
Gel 24 V
Not available
Not available
NiCad 12 V
Not available
Not available
Charger Equalize
Stage Duration (Min.)
NiCad 24 V
Not available
Not available
The setting for the maximum amount of time
spent in equalize. This prevents excessive
outgassing and avoids boiling out the
battery.
Default 12 V
Not available
Not available
Default 24 V
Not available
Not available
FLA 12 V
0 – 99
0
FLA 24 V
0 – 99
0
AGM 12 V
Not available
Not available
AGM 24 V
Not available
Not available
Gel 12 V
Not available
Not available
Gel 24 V
Not available
Not available
NiCad 12 V
Not available
Not available
Charger Charge
Cycles Between Auto
Equalize Cycles
NiCad 24 V
Not available
Not available
When automatic equalize cycle enable is
active, this setting determines the number of
charge cycles between equalize cycles.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler GM87448 and is the answer not in the manual?

Kohler GM87448 Specifications

General IconGeneral
BrandKohler
ModelGM87448
CategoryPortable Generator
LanguageEnglish

Related product manuals