2.  Connect  brush  leads  in  series  with  12-Volt  battery  and 
DC  ammeter  as  shown  in  Figure  6-37. 
3.  Ammeter  reading  should  approximate  battery  voltage 
divided  by  specified  rotor  resistance  (Table  6-1). 
4.  Record  ammeter  reading. 
5.  Start  generator  set  and  run  at  NO  load. 
6.  Observe  ammeter  with  unit  running.  If  current  increases 
considerably,  a running  short  in  the  rotor  has been  detected. 
EXCITER  / 
VOLTAGE  r  1 
REGULATOR  ,-‘&I; 
DC 
BATTERY 
SLIP  RINGS  J  BRUSHES 
Figure  6-37.  Separate  Excitation  Connections 
6-l  1.  VOLTAGE  SENSING  RELAY 
erator  output,  and  disconnect  excitation  current  from  the 
battery  to  the  regulator  and  field  (V.B.U.),  and  energize  the 
3CR  (interlock  relay).  If  there  is  no  AC  output;  the  relay 
will  not  energize,  and  the  unit  will  shut  down  when  the 
start-stop  switch  is  released  from  the  start  position. 
6-12.  GENERATOR  REASSEMBLY 
1.  On  the  3.5kW,  apply  antiseize  compound  to  the  rotor 
threads  (Figure  6-39).  Thread  the  rotor  onto  the  drive 
shaft,  and  tighten  by  hand. 
2.  On  the  4SkW,  55kW,  7kW  or  7.5kW,  apply  antiseize 
compound  to  the  crankshaft  stub  (Figure  6-40).  Install  the 
rotor  onto  the  crankshaft  with  the  thru  bolt.  See  Table  6-2 
for  torque  value. 
I 
SIZE 
I 
TORQUE 
I 
5116 
3/8 
l/2 
100  to  125  in.  Ibs.  (11.3-14.1Nm) 
175  to  200  in.  Ibs.  (19.8-22.6Nm) 
40  to  55  ft.  Ibs.  (54.2-74.6Nm) 
Table  6-2.  Generator  Thru  Bolt  Torque 
3.  Slide  the  stator  into  position  making  sure  the  leads  are 
at  12  o’clock  position  (Figure  6-41). 
4.  Install  the  end  bracket  with  the  four  long  over  bolts. 
5.  Position  the  brush  holder  and  install  the  two  brush 
holder  screws.  To  install  the  brush  holder,  it  will  be 
The  voltage  sensing  relay  (Figure  6-38)  is  located  in  the 
necessary  to  retain  the  brushes  with  a wire  (Figure  6-42). 
end  bracket  assembly.  Its  function  is  to  sense  AC  gen- 
Remove  the  wire  when  the  brushes  are  installed. 
’ TO  PIN  “4”  OF 
PI  CONNECTOR 
TO  LEAD  FROM  “B” 
TERMINAL  OF 
VOLTAGE  REGULATOR 
I 
I 
COIL  RESISTANCE  =  4000  OHMS 
COIL  VOLTAGE  =  120  VOLTS  AC 
Figure  6-38.  Generator  Voltage  Sensing  Relay  (VSR) 
6-12