TP-6487 8/0712 Section 1 Description
1.3 Specifications
Enclosure Type Rating, Amps Load Center Weight, kg (lb) HxWxD,mm(in.)
NEMA 1 150–225 40 circuits 11.40 (25.0) 1000 x 362 x 95 (39.37 x 14.25 x 3.74)
NEMA 3R 100–200 28 circuits 19.10 (42.0) 858 x 375 x 115 (33.78 x 14.76 x 4.53)
Figure 1-2 Weights and Dimensions
Item
Specifications
Type 1 enclosure, 150–225 amp. Maximum rating of generator circuit breaker is 125 amp.
For indoor installation, flush or surface mount. Up to 40 branch circuits.
Enclosures and ratings
Type 3R enclosure, 150–200 amp. Maximum rating of generator circuit breaker is
125 amp. For indoor or outdoor installation, padlockable. Up to 28 branch circuits.
150, 200, and 225 amp models are suitable for service entrance use.
Two-pole, single-phase open-transition transfer mechanism.
240 VAC 60 Hz.
Trans
er mechanism
Solid neutral.
Manually operable.
Operating temperature
–10° to 60° C(14° to 140° F) with derating
–10
° to 40° C(14° to 104° F) without derating.
Storage temperature
–40° to 85° C (–40° to 185° F).
Humidity 5%--95% noncondensing.
Altitude 0--2000 m (0--6560 ft.).
Vibration and shock (shipping) ISTA-tested per ASTM 4169-1A.
UL listed per UL 67, Enclosed Panelboards.
Certifications, codes, and
Tested to UL 1008, Standard for Automatic Transfer Switches for Use in Optional Standby
Systems.
standards
NFPA 70, National Electrical Coder, Article 702.
NEMA Standard IC10-1993, AC Automatic Transfer Switches.
IEC 61000-4-2, 2001, Electrostatic Discharge, Level 3.
IEC 61000-4-3, 2002, Radiated Immunity, Level 2.
IEC 61000-4-4, 2001, EFT/Burst Immunity, Severity Level 3.
EMI/EMC immunity
IEC 61000-4-5, 2001, Surge Immunity, Severity Level 4.
IEC 61000-4-6, 2003, Conducted RF Immunity, Level 2.
FCC Part 15, Radiated Emissions, Class B.
FCC Part 15 using CISPR 11 Conducted Emissions, Class B.
Figure 1-3 Specifications