TP-6487 8/07 13Section 2 Operation
Section 2 Operation
2.1 Introduction
Red and green LEDs on the transfer switch controls
indicate which sources are available, show which
source is connected to the load, and flash to indicate
fault conditions. Pushbuttons allow you to start and stop
the generator set (with or without transferring the load)
and set the exercise timer. See Figure 2-1.
The transfer switch uses factory-default settings for time
delays, voltage and frequency pickup and dropout, and
other system settings. An optional accessory board
allows changes to the time delays and exerciser settings
and provides connections for remote test and remote
exercise inputs. See Section 4.1 for information on the
accessory board.
2.2 Pushbuttons and Indicators
Figure 2-1 identifies the controller pushbuttons and LED
indicators.
The LEDs light steadily or flash to indicate different ATS
conditions as shown in Figure 2-2. See Section 2.5 for
more information on fault conditions.
tp6345
Utility Source Position LED
Utility Source Available LED
Generator Position LED
Generator Source Available LED
Test Button Exercise Button
Figure 2-1 User Interface Panel
Condition LED Indication
Utility source power available Utility Source Available LED lights steadily.
Load connected to utility power Utility Source Position LED lights steadily.
Generator set power available GEN Source Available LED lights steadily.
Load connected to the generator set GEN Position LED lights steadily.
Loaded test GEN Available and GEN Position LEDs flash on 1 second, off 1 second.
Unloaded test GEN Available LED flashes on 1 second, off 1 second.
Loaded exercise GEN Available and GEN Position LEDs flash on 0.5 second, off 2 seconds.
Unloaded exercise GEN Available LED flashes on 0.5 second, off 2 seconds.
Failure to acquire standby source fault GEN Available LED flashes 2 times/second.
Failure to transfer fault GEN or Utility Source Position LED flashes 2 times/second.
Auxiliary switch failure fault GEN Position and Utility Source Position LEDs flash 2 times/second.
Figure 2-2 LED Indication