SELF-DIAGNOSTIC ALARM CODES
Alarm Code Possible Causes What To Do
Compressor
overload
• High ambient
temperature
• Unstable power
supply
• Defecve
compressor
• Ambient temperature
must be under 45°C(113°F)
• Check the power supply
• Contact a qualied
service agent
Out of phase
Incorrect power cable
connecon
Re-connect the power cable
to the correct power source
Drain pump
(Applicapable for
unit with drain
pump)
• Defecve drain
pump
• Improper water
circulaon
• Check the hose connecon
from drain pump
• Replace the drain pump
• Contact a qualied service
agent
High pressure
• Improper air
circulaon
• High ambient
temperature
• Clean the air lter
• Ensure exhaust duct is not
blocked or kinked
• Ambient temperature must
be under 45°C(113°F)
Low Pressure
• Refrigerant leak
• Low ambient
temperature
• Contact a qualied
service agent
Table 1- Alarm Codes