GP800 UPS SPECIFICATION
- 35 -
Model 1KVA 2KVA 3KVA 4KVA 6KVA 8KVA 10KVA
Internal protection equipment LCD panel
Battery
UPS automatically shutdowns when battery is low power level, there is no
fuse switch protection.
Overload
When load reaches 110~150% of rating, transfer to bypass after 30s,
recover auto.
Over-tempera
ture
Automatically transfer to bypass if UPS internal temperature > 85
Output
short-circuit
Limit current, automatic shutdown, fuse and there no fuse switch
protection.
UPS
abnormal
Automatically transfer to bypass and supplied power by utility
Noise filter 10~100KHz at 40Db; 100KHz~100MHz at 70dB
LCD display
Display: input, output voltage, frequency, battery voltage,
output power (%), temperature
Battery BVL One LED, it lit on when battery low voltage
Environment
Temperature 0~40
Humidity 20~90% non-condensing
Noise <58dB (1m away from enclosure)
General
Output socket Terminal plate
Unit weight
(standard
battery)
46Kg 63Kg 75Kg 65Kg 69Kg 105Kg 115Kg
Dimension
(mm)
W×D×H
231×662×540
231×627×720 305×652×866
Others
Full
efficiency
>85%
Transform
time when
utility fault
0s
UPS status
indicator light
Utility, inverter, bypass, UPS abnormal (fault)
Communicati
on interface
RS232 interface