10 Installation Manual 2014 - Riv 2
Rated power input and fuse information
Model Rated Outdoor Unit Indoor Unit Combined System
Hz Volts Watts
Max
Current
Amps
Max
Fuse
Rating
Amps
Watts
Max
Current
Amps
Max
Fuse
Rating
Amps
Watts
Max
Current
Amps
Max
Fuse
Rating
Amps
LC 07 50 220-240 3300 14 16 3054 14.4 16 6354 28.4 32
LC 10 50 220-240 4900 21 32 3054 14.4 16 7954 35.4 40
LC 12 50 220-240 6000 26 32 4054 17.4 20 10054 43.4 50
LC 15 50 220-240 6800 29 32 4054 17.4 20 10854 46.4 50
Please note:
● Indoorunitloadincludesbackupheater bu t n o t p um p ( 54Wr a t ing ) .
● Indoorandoutdoorunitscanbes upp lie d s e pa r a t el yo r o n o n e de di c a t ed s u ppl y but
slave unit should be suitably fused down.
● Shieldedheatresistantcablet o b e ins t a l le d o n EL V c a ble s .
● 300mmspacingshouldbeensuredbetwe en un s hie ld ed 230VandallELVcables
where practicable.
● LC12KWandLC15KWExternalUnitsshould be s upp lie d viam o t o r r a t ed M .C.B’S.
On completion of Electrical Installation please ensure the following:
● 230VandELVcablesaresuitablyc o nn ec t e d in a pp ro p ria t e c o n ne c t io n blo c ks.
● DipswitchestobothInternaland exte rn a l uni t s a re c o rre c t ly s e t . See p a g e 15
● ELVconnections7/8,9/10,11/12arelinkedout i funus e d.
● ElectricheaterswitchinInternalUni t ( whe re a p pli c a ble ) is s wit c h ed ‘ o n’ .