3 For Your Safety
3.6.3 Checking Burner Sequencer Part
Check the following:
Correct setting of time parameters (especially safety and pre-purge periods).
Whether an ionisation or approved self-checking flame sensor is used as only these types
allow continuous operation.
Functioning of flame sensor
in case of flame blow-off during operation
parasitic light being present during pre-purge period
missing flame formation at the end of the safety-period
Check the performance of all available and/or essential incoming signals, such as:
Air pressure switch
Gas pressure - min./oil pressure - min.
Safety interlock chain (e.g. STB)
Activated leakage control function for gas valves if required for application purposes.
If necessary, ensure a correct leakage quantification.