Page #41 background image
40
6 Correcting Faults
6.1.2 Warnings
Warning no. Warning text
001 (HP)
101 (ÜP)
O
2
offset voltage in the air too large or too small
/1 - 29999 Trigger value of the O
2
offset voltage in the air (x0.1 mV)
003 (HP)
103 (ÜP)
O
2
temperature too large or too small, was not assumed
invalid calibration (p. ex. with calibration gas >14,9 Vol % O
2
). The new
O
2
temperature is not accepted. The O
2
measurement remains/will be
improper.
/1 - 29999 Trigger value of the O
2
temperature (x0.1 K)
010 (HP)
110 (ÜP)
For LT3-F: Internal resistance of ceramics of the O
2
electrode
over 45 Ω
For LT3: Internal resistance of ceramics of the O
2
electrode
over 80 Ω
/0 - 65535 Trigger value of current internal resistance (x0.1 ),
tolerance time of 3 seconds.
016 (HP)
116 (ÜP)
Internal warning
/1 Serial number, customer ID or service password reset.
Contact the manufacturer.
Display if customer ID in LT3 and UI do not correspond.