EasyManua.ls Logo

Lauda IN 530 T - Configure Potential-Free Contact (Alarm Output); Interface Potential-Free Contact

Default Icon
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Equipment connected to the low-voltage inputs and outputs must
be safely insulated against dangerous contact voltages as per DIN
EN 61140, for example, using double or reinforced insulation as per
DIN EN 60730-1 or DIN 60950-1.
Refer to the separate operating manual accompanying the inter-
face modules for further information on installing and operating
these interface modules. Each respective operating manual must be
observed in order to use the module as intended.
4.7.1 Configure potential-free contact (alarm output)
In the Alarm output menu, an option is always selected. The selected option
is marked with a check mark. You can combine the other options.
A fault in the device can be an alarm or an error.
Table 8: Possible options
Options Description
Fault Signal transmission (e.g. for reverse flow pro-
tection, pilot lamp)
Safe Mode Activation of Safe Mode (Safe Mode must be
switched on beforehand in the device menu)
Standby Switch device into standby
Personnel:
n
Operating personnel
1. Switch to the main menu.
2.
Select the Setup Basic setup Alarm output menu item.
3. The following options are available:
n Fault
n Safe Mode
n Standby
4. Press the Enter key to confirm your selection.
4.7.2 Interface potential-free contact
n The contacts may be loaded with a maximum voltage of 30 V direct
current (DC) and a maximum current of 0.2 A.
V6 Integral Process Thermostats and High-Temperature Thermostats 45 / 198

Table of Contents

Related product manuals