Data Value Unit
Transport temperature range -20 ... 60 °C
Operating temperature
range
Dimensions (W x D x H) Weight
°C mm kg
MC 250 -10 ... 40 200 x 350 x 465 26
MC 600 -10 ... 40 350 x 480 x 595 51
MC 1200 -10 ... 40 450 x 550 x 650 64
MC 1200 W -10 ... 40 450 x 550 x 650 64
11.2
Refrigeration unit
Cooling capacity
Cooling
capacity
(20 °C)
Cooling
capacity
(10 °C)
Cooling
capacity
(0 °C)
Cooling
capacity
(-10 °C)
Refrigerant
kW kW kW kW
MC 250 0.23 0.2 0.15 0.09 R134a
MC 600 0.6 0.5 0.36 0.15 R134a
MC 1200 1.15 1.05 0.75 0.4 R134a
MC 1200 W 1.15 1.05 0.75 0.4 R134a
The cooling capacity is measured for a specified temper-
ature of the heat transfer liquid. Information is provided
in brackets. The ambient temperature for the measure-
ment is 20 °C; ethanol was used as heat transfer liquid.
The cooling water temperature is 15 °C and the cooling
water differential pressure is 3 bar for the measurement
of water-cooled devices.