11
460 VOLT MICRO SERIES RATINGS
MODEL
INPUT OUTPUT
(400/480 Vac, 50-60 Hz) (0-400/460 Vac)
FOR MOTORS NOMINAL NOMINAL
CATALOG RATED INPUT CURRENT POWER CURRENT POWER
NUMBER HP kW PHASE (AMPS) (KVA) (AMPS) (KVA)
174920
174939* 1 0.75 3 2.8/2.4 2.0 2.3/2.0 1.6
174532**
174921
174940* 2 1.5 3 4.7/4.1 3.4 3.9/3.4 2.7
174533**
174922
174941* 3 2.2 3 6.8/5.7 4.7 5.5/4.8 3.8
174534**
174923
174942* 5 3.7 3 10.2/8.9 7.3 8.7/7.6 6.1
174535**
174924
174548* 7.5 5.5 3 14.7/12.8 10.6 12.6/11.0 8.8
174745**
174552
174554* 10 7.5 3 18.3/15.9 13.2 16.0/14.0 11.2
174747**
174558
174749* 15 11 3 28/24 19.8 24/21 16.7
174750**
174561
174752* 20 15 3 36/31 25.3 31/27 21.5
174753**
174563
25 18.5 3 44/38 31.9 39/34 27.1
174755*
174565
30 22 3 52/45 37.6 46/40 31.9
174757*
174567
40 30 3 68/59 49.0 60/52 44.0
174513*
174593
50 37 3 85/74 61.5 75/65 51.8
174511*
174572
60 45 3 100/87 72.3 88/77 61.3
174574*
NOTE See Section 8.0 for recommended fuse type.
* = NEMA 4/12 or 12 ENCLOSURE
** = NEMA 4X ENCLOSURE
OTHERS ARE NEMA 1 ENCLOSURE