63 SOFTWARE (SOFTWARE VERSION)
This parameter displays the software code and revision number of the control board software. This
information is useful when contacting the factory for programming or troubleshooting assistance. This is a
"view-only" parameter, and cannot be changed.
Set Point Control (PID): Micro Series drives with software version M108305 or higher (as seen in Parameter
63 - SOFTWARE) are capable of PID Setpoint control, but the feature is normally “hidden” and must be
activated using a special password. Contact LEESON for the password and instructions describing how to
unlock the PID feature and use it for process control.
64 MONITOR (MONITOR)
This parameter is used to enable (ON) or disable (OFF) the MONITOR MODE function. The
functionality is explained below:
ON Pressing the PROG/RUN key will call up the PASSWORD prompt. If the ENTER key
is pressed while the password value reads 0000, the MONITOR MODE is entered and
parameters can be viewed (except for PASSWORD), but not changed.
OFF Pressing the PROG/RUN key will call up the PASSWORD prompt. If the ENTER
KEY is pressed while the password value reads 0000 (or any other incorrect value),
it will be treated as in incorrect password and the display will flash ERROR:
INCORRECT, and then return to the PASSWORD prompt to allow another attempt
at entering the correct password.
65 PROGRAM (PROGRAM FACTORY DEFAULTS)
STOP (TB-1) and EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters are
reset to factory defaults! The drive must be reprogrammed after a RESET in order to insure
proper operation.
FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/OR INJURY
TO PERSONNEL!
This parameter is used to reset the programmable parameters back to the factory default settings. This
parameter has four possible settings:
MAINTAIN Maintain parameter settings as they are.
RESET 60 Resets parameters to factory defaults for 60 Hz base frequency.
RESET 50 Resets parameters to factory defaults for 50 Hz base frequency.
RST HIGH Resets parameters to factory defaults for 650 Hz base frequency. This option will only
appear if the drive is equipped with the High Frequency Output option.
When a factory reset is performed, the following terminals are affected:
67
WARNING