EasyManua.ls Logo

LEGRAND DAKER DK Plus 3 101 73 - Page 71

LEGRAND DAKER DK Plus 3 101 73
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71
DAKER DK Plus
5 kVA - 6 kVA - 10 kVA
Installation manual
3 101 75 3 101 76 3 101 77 3 101 78
General characteristics
Nominal power (VA) 5000 6000 10000 10000
Active Power (W) 5000 6000 10000 9000
Technology on-line, double conversion, VFI-SS-111
Waveform sinusoidal
Bypass
internal automatic bypass
external maintenance bypass
(optional)
external bypass
line (dual input)
internal
automatic
bypass
external
maintenance bypass
(optional)
Transfer time
AC to DC
0 ms
Input characteristics
Input Connection terminal strips
Rated input voltage 230 V
380 V
Range of input
voltage
from 176 V to 280 V at full load
from 305 V
to 485 V
at full load
Rated input
frequency
50 / 60 Hz ± 5 %
Maximum input
current
27.5 A 33 A 56 A 54 A
Total harmonic
distortion of the
input current
THDi < 3%
Input power factor ≥ 0.99 (with full linear load)
≥ 0.9 (with full
linear load)
Number of
input phases
Single-phase
Three-phase
Output characteristics
Outlets terminal strips
Rated output voltage
230 V ± 1%
adjustable to 200/208/220/230/240 V
Rated output
frequency
50 / 60 Hz ± 0,1%