EasyManua.ls Logo

LEGRAND Wattstopper DT-305 User Manual

LEGRAND Wattstopper DT-305
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Wattstopper
®
360° Dual Technology • Low Voltage Occupancy Sensor (version 3)
with Manual On feature
Double technologie à 360° • Détecteur de présence basse tension (v3)
avec les fonctionnalité de marche manuelle
Doble tecnología de 360° • Sensor de presencia de bajo voltaj (v3)
con función de encendido manual
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 23948 – 07/18 rev. 5
Catalog Number • Numéro de Catalogue • Número de Catálogo: DT-305
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DT-305 -U is BAA and TAA compliant (Product produced in the U.S.)
UNIT DESCRIPTION
The Wattstopper DT-305 360° Dual Technology occupancy
sensors combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combination of these technologies
helps to eliminate false triggering problems even in difficult
applications.
The DT-305 turns lighting systems on and off based on
occupancy. The DT-305 provides numerous operating modes that
can be combined to create the ideal custom control. The sensors
can be configured to turn lighting on, and hold it on as long as
either or both technologies detect occupancy. After no movement
is detected for a user specified time (30 seconds to 30 minutes)
the lights are switched off. A “walk-through” mode can turn lights
off after only 3 minutes, if no activity is detected after 30 seconds
of an occupancy detection.
The DT-305 operates on 24V, supplied by Wattstopper Power
Packs.
SPECIFICATIONS
Voltage ......................................................18–28VDC/VAC half rectified
Current Consumption @24VDC/VAC ..................16mA (DC), 69mA (AC)
Power Supply ..................................................Wattstopper Power Packs
Isolated Relay Rating ...................................................1A @30VDC/VAC
Operating Temperature .................................... 32° to 131°F (0° to 55°C)
Time Delay Adjustment ................................... 30 seconds to 30 minutes
Walk-Through Mode .......................... 3 minutes if no activity after 30 sec
Test Mode ....................................................5 sec. upon DIP switch reset
PIR Coverage (Typical) ................................................................1300 ft²
Sensitivity Adjustment ....................High or Low (DIP switch setting)
Ultrasonic Coverage (Typical) ......................................................1300 ft²
Sensitivity Adjustment ................................ Min. to Max. (trimpot)
Frequency ..........................................................................40kHz
UL & CUL Listed for use with Wattstopper Power Packs
COVERAGE PATTERN
The DT-305 provides a 360° coverage pattern. The coverage shown represents walking motion at a mounting height of 8-12 feet. For
building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. The coverage for PIR ONLY
trigger mode varies with mount height. Refer to pattern below for details. Ultrasonic coverage is roughly the same for 8-12 foot mount
heights. Refer to PIR and Ultrasonic trigger mode coverage for details.
Side View
8’ (2.4m)
10’ (3m)
12’
(3.7m)
0
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
0
PIR Only Coverage
Top View
36 ft
(10.97m)
36 ft x 36 ft
(10.97m x 10.97m)
PIR
Coverage
Ultrasonic
Coverage
Drawings not to scale, representative of PIR and
Ultrasonic Trigger Mode major motion coverage.
8-12 foot Mounting Height
Question and Answer IconNeed help?

Do you have a question about the LEGRAND Wattstopper DT-305 and is the answer not in the manual?

LEGRAND Wattstopper DT-305 Specifications

General IconGeneral
TypeOccupancy Sensor
CategoryAccessories
MountingCeiling
Light Level SensorYes
Voltage120-277V AC
Sensor TechnologyPIR (Passive Infrared)
Time DelayAdjustable from 30 seconds to 30 minutes
Operating ModesOccupancy, Vacancy
Operating Temperature0°C to 50°C
TechnologyDual Technology (PIR and Ultrasonic)
Mounting HeightUp to 12 ft
Ambient Temperature Range0°C to 50°C
Humidity Range0% to 90% RH (non-condensing)
Dimensions4.5" dia x 2.5" H (114 mm dia x 64 mm H)
Weight0.5 lbs (0.23 kg)
Coverage AreaUp to 900 sq ft (84 sq m)

Summary

UNIT DESCRIPTION

Product Overview

Combines PIR and ultrasonic technologies for advanced occupancy sensing.

SPECIFICATIONS

Technical Details

Lists voltage, current, temperature, and coverage specifications.

COVERAGE PATTERN

Coverage Diagrams

Visuals showing PIR and Ultrasonic coverage patterns.

PLACEMENT GUIDELINES

Optimal Sensor Positioning

Advice on placing the sensor for best coverage and avoiding interference.

WIRING DIRECTIONS

Low Voltage Connections

Connecting the sensor to the power pack and common terminals.

Manual Switch Wiring

Wiring the sensor for manual ON/OFF functionality with a switch.

Isolated Relay Connection

Using the isolated relay for external control applications.

MOUNTING THE SENSOR

Ceiling Mount Installation

Attaching the sensor directly to an acoustic ceiling tile.

J-Box Mount Installation

Mounting the sensor to an octagonal J-Box.

SENSOR ADJUSTMENT

Testing Occupancy Sensors

Procedure for testing sensor functionality using LEDs.

MANUAL ON FUNCTION

Manual Mode Operation

How the sensor operates in Manual Mode with switch activation.

Automatic Mode Operation

How the sensor operates in Automatic Mode with switch and occupancy.

DIP SWITCH SETTING

Time Delay Configuration

Setting the time delay for lights to remain on after no motion.

Walk-Through Mode

Enabling or disabling the walk-through mode for faster turn-off.

PIR Sensitivity Adjustment

Adjusting the PIR sensor's detection range.

Occupancy Logic Configuration

Setting occupancy detection logic for initial and sustained presence.

OVERLOAD PROTECTION

Overload Indicator

Visual indication of overload condition via blinking LEDs.

TROUBLESHOOTING

Power and LED Issues

Diagnosing power, no LED activity, and red LED not flashing problems.

Detection and Lighting Issues

Resolving green LED, lights not turning on, and automatic turn-off problems.

SERVICE

Service Mode

Bypassing occupancy controls for manual operation via a light switch.

ORDERING INFORMATION

Product Catalog Numbers

List of catalog numbers for sensors and power packs.

WARRANTY INFORMATION

Product Warranty Details

Information on the five-year warranty for Wattstopper products.