Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: DW-311/DW-311-347
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
Wattstopper
®
Dual Technology 0–10 Volt Wall Switch Occupancy Sensor (version 2)
Interrupteur mural 0–10 Volt avec détecteur de mouvement à double technologie (v2)
Sensor de ocupación con interruptor de pared y tecnología doble de voltaje 0 a 10 (V2)
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 26167 – 3/19 rev. 4
SPECIFICATIONS
Voltages:
DW-311 .................................................120/277 VAC, 50/60 Hz
DW-311-347 .................................................347 VAC, 50/60 Hz
Load Limits:
@120 VAC......... 1000-W tungsten ballast, E-ballast, LED, 1/4 HP
@277 VAC ................... 1200-W ballast, E-ballast, LED, 1/4 HP
@347 VAC .....................................1500W ballast, LED, 1/4 HP
Time Delay Adjustment ..................................................3 to 30 minutes
Walk-Through Mode ....................... 3 minutes if no activity after 30 sec.
Test Mode ............................................. 10 min. with 10-sec. time delay
PIR Adjustment .................................................................... High or Low
Ultrasonic Adjustment .....................Minimum to Maximum (trimpot), Off
Alerts ........................................................Selectable Audible & Visual
Multi-Way Capability ...............................................................All models
Terminal screw torque ............................................ 16 lbf-in (18 kgf-cm)
High Trim ................................................................................... 6 to 10V
Low Trim ......................................................................................0 to 4V
Ramp Up .......................................................................1 to 10 seconds
Fade Down ................................................................. 2.5 to 30 seconds
DESCRIPTION AND OPERATION
The DW Dual Technology Multi-Way Wall
Switch sensors combine advanced passive
infrared (PIR) and ultrasonic technologies
into one unit. The combined technologies
help to eliminate false triggering even in
difficult applications.
The DW sensor has Multi-Way
available on all models.
A “walk-through” mode can turn lights
off after only 3 minutes, if no activity is
detected after 30 seconds following an
occupancy detection.
The DW-311 has one relay with
dimming control capability and two
buttons to allow control of the dimming.
DW sensors contain a light level
sensor. If adequate daylight is present,
the sensor holds the load OFF until
light levels drop, even if the area
is occupied. See the Light Level
Adjustment section.
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
INSTALLATION
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the DW flying leads as shown in the wiring diagram
that is appropriate to the DW model and electrical supply. The ground
wire (green) must be fastened to ground for the sensor to work
properly.
3. Attach the sensor to the wall box by inserting screws into the two wide holes on the
top and bottom of the attached metal bracket. Match them up with the holes in the wall
box and tighten. Do not use excessive force when installing the sensor into the
wallbox. Doing so can bend the mounting strap which can affect button operation.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch and
the lights will turn ON. There is a delay due to initial power-up of the sensor that only
occurs during installation.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not included).
Driver
or Ballast
Red
Black
Neutral
Line
Green
White
Ground
Violet
Yellow
Gray
0-10V
Dimming
DW-311 and DW-311-347 Wiring
#12 – #14 AWG
Strip Gage
1/2"
12.7mm
Cu Wire Only
8" flying leads for
line, load, ground
and multi-way
connections
White
Red
Green
Yellow
Violet
Grey
Black
Black
Violet
Black
Neutral
White
Line
White
Ground
Green
Ground
Green
Yellow
traveler
Yellow
Red
Gray
Red
Violet
Gray
Connect 0-10V
leads to dimming
ballast from one
DW-311 only
Driver
or Ballast
Typical Multi-Way Wiring
(DW-311 or DW-311-347 up to 4 sensors)
WARNING: Grounding the violet and gray wires can damage the
unit. Do not apply power to the sensor until all wires are connected or
capped off if the driver is to be installed at a future time.
Question and Answer IconNeed help?

Do you have a question about the LEGRAND Wattstopper DW-311-I and is the answer not in the manual?

LEGRAND Wattstopper DW-311-I Specifications

General IconGeneral
BrandLEGRAND
ModelWattstopper DW-311-I
CategoryAccessories
LanguageEnglish

Summary

Description and Operation

Specifications

Installation

Coverage Patterns

PIR Sensor

Details the two-tiered, multi-cell Fresnel lens with 180-degree field of view and red LED motion detection.

Masking the Lens

Explains how to use opaque tape to mask sections of the PIR sensor's view to eliminate unwanted coverage.

Multi-Way Functionality

Button Functions

Sensor Adjustment and Features

Additional Programmable Features

Alerts

Describes audible and/or visible alerts that warn before the load turns off, with default settings.

Walk-Through Mode

Shortens time delay to reduce ON time after brief occupancy, turning load OFF after 3 minutes if no motion.

PIR Sensitivity Adjustment

Allows manual selection of PIR sensitivity to avoid false detections or improve coverage in challenging environments.

High and Low Trim

Adjusts maximum and minimum dimming amounts, with default values of 100% and OFF respectively.

Ramp Up and Fade Down Time

Light Level Adjustment

Power Loss Mode

Presentation Mode

Service Mode

Preset On Level

Non-Dim Mode

Reset to Factory Default

DIP Switch Settings

Troubleshooting

Lights Do Not Turn ON with Motion (LED Flashes)

Addresses issues where lights fail to turn on despite the PIR LED flashing, checking wiring and ON mode.

Lights Do Not Turn ON with Motion (LED Does Not Flash)

Troubleshoots lights not turning on when motion is detected and the PIR LED is not flashing, checking sensitivity and line.

Lights Do Not Turn OFF

Provides steps to diagnose why lights do not turn off, including checking time delay and sensor placement.

Sensing Motion Outside Desired Areas

Offers solutions for unwanted motion detection, suggesting lens masking and sensitivity adjustments.

Red LED is OFF

Diagnoses the issue of the red LED being off, indicating potential problems with Service Mode or Time Delay settings.