EasyManua.ls Logo

LEGRAND Wattstopper CI-355 User Manual

LEGRAND Wattstopper CI-355
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Wattstopper
®
360° Passive Infrared Line Voltage Occupancy Sensor (version 3)
with Light Level Feature
Détecteur de présence de tension de ligne infra-rouge passif à 360° (v3)
avec fonction niveau de luminosité
Sensor de ocupación infrarrojo pasivo de 360° voltaje de línea (v3)
con función de nivel de luz
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24055 – 02/17 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: CI-355
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
SPECIFICATIONS
Voltages ......................................................120//230/277/347VAC, 50/60Hz
Load Ratings
@120VAC ........................................0-800W Ballast/Tungsten/LED
@230VAC (Single Phase)...............................0-1200W Ballast/LED
@277VAC .....................................................0-1200W Ballast/LED
@347VAC ......................................................0-1500W Ballast/LED
Operating Temperature ........................................ 32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ............................................10FC–300FC
Time Delay Adjustment ....................................... 30 seconds to 30 minutes
Walk-Through Mode ................. 3 minutes if no activity after 30 sec.
Test Mode ............................................5 sec. upon DIP switch reset
PIR Coverage
Model CI-355 ................................................................ up to 1200ft
2
Model CI-355-1 .............................................................. up to 500ft
2
Sensitivity Adjustment ...............................High or Low (DIP switch)
DESCRIPTION AND OPERATION
The Wattstopper CI-355 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and
ambient light levels. The light level feature can be used to keep lights from turning on if the ambient light level is sufficient.
The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is
detected for a user specified time (30 seconds to 30 minutes) the lights are switched off. A “walk-through” mode can turn lights off after
only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection.
The CI-355 operates on 120VAC, 230VAC (1Ø), 277VAC, or 347VAC.
COVERAGE PATTERN
The CI-355 provides a 360° coverage pattern. Two lens patterns are available. The CI-355 provides up to 1200 square feet of coverage
and the CI-355-1 provides up to 500 square feet of coverage. The coverage shown represents walking motion at a mounting height of
8 feet. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease.
IW
P
8’ (2.4m)
10’ (3m)
12’
(3.7m)
0
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
0
CI-355 Coverage Pattern (standard lens)
Side View
Top View @ 8ft
8’ (2.4m)
10’ (3m)
12’ (3.7m)
0
20’
(6.1m)
15’
(4.6m)
10’
(3m)
5’
(1.5m)
0 20’
(6.1m)
15’
(4.6m)
10’
(3m)
5’
(1.5m)
24 ft
7.3m
CI-355-1 Coverage Pattern (high density, reduced range lens)
Side View
Top View @ 8ft

Questions and Answers:

LEGRAND Wattstopper CI-355 Specifications

General IconGeneral
CategoryOccupancy Sensor
TechnologyPassive Infrared (PIR)
Voltage24V DC
Coverage360°
MountingCeiling
Mounting Height8-12 ft
Ambient Temperature Range32°F to 104°F (0°C to 40°C)
TypeOccupancy Sensor
Time DelayAdjustable 30 sec to 30 min
Dimensions4.5" diameter x 1.5" deep
Weight0.3 lb
CertificationsUL, cUL
Accessory TypeOccupancy Sensor

Summary

Specifications

Description and Operation

Coverage Pattern

CI-355 Coverage Pattern (standard lens)

Details the 360-degree coverage area for the standard lens.

CI-355-1 Coverage Pattern (high density, reduced range lens)

Details the coverage area for the high-density, reduced range lens.

Placement Guidelines

Wiring Directions

Mounting the Sensor

Using a 4-Inch Square Junction Box with Double-Gang Mudring

Instructions for mounting the sensor using a 4-inch square junction box.

Using an Octagonal Junction Box

Instructions for mounting the sensor using an octagonal junction box.

Sensor Adjustment

Light Level Features

Setting Light Level

Procedure to calibrate and set the ambient light level for the sensor.

Disabling Light Level

Procedure to reset the light level feature to its default maximum setting.

DIP Switch Setting

Troubleshooting

Ordering Information

Warranty Information