EasyManuals Logo

Lennox 14ACX User Manual

Lennox 14ACX
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
CHARGING INFORMATION
FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION INSTUCTION.
AIRFLOW CHECK - Both airflow and refrigerant charge must be monitored
for a proper system set‐up. It may be necessary to alternately check and
adjust the airflow and the refrigerant charge.
NOTE - Be sure that filters and indoor and outdoor coils are clean before testing.
To determine temperature drop across indoor coil (Delta-T), measure the entering air dry
bulb (DB) and wet bulb (WB) temperatures at the indoor coil. Find Delta-T in table 1. Measure
coil's leaving air DB and subtract that value from entering air DB. The measured difference
should be within +
3ºF (+1.8ºC) of table value; if too low, decrease the indoor fan speed (refer
to indoor unit for information). If the Delta-T is too high, increase the indoor fan speed. Repeat
charging procedure and Delta-T (air flow adjustment) procedure until both are correct.
Example: assume entering air DB - 72, WB - 64, leaving DB - 53. Therefore, Delta-T should
be 15 (per table); delta across coil is 72 - 53 or 19 (which is 4ºF higher than table value); action
necessary: increase fan speed.
Table 1. Evaporator Coil Delta-T
Dry bulb 80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
temperature 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
of air 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
entering 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
indoor 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
coil (ºF) 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70
[ Wet bulb temperature of air entering indoor coil ]
Table 2. Superheat (SH) Value RFC System - +5ºF
40 15 18 20 23 26 29 32 34 38 41 43 46 48 51
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49
50 11 14 16 19 22 25 28 31 34 37 39 42 44 47
Dry bulb 55 9 12141720232730333638404244
temperature 66 7 10121518212427303335384043
of ambient 65 6 10 13 16 19 21 24 27 30 33 36 38 41
air entering 70 7 1013161921242730333639
outdoor 75 6 9 121518212428313437
unit (ºF) 80 5 8 12 15 18 21 25 28 31 35
85 ‐‐‐‐‐‐811151922263033
90 ‐‐‐‐‐‐59131620242731
95 ‐‐‐‐‐‐‐6101418222529
100 ‐‐‐‐‐‐‐‐81216212428
105 ‐‐‐‐‐‐‐‐5913172226
110 ‐‐‐‐‐‐‐‐‐611152025
115 ‐‐‐‐‐‐‐‐‐‐8141824
ºF 50 52 54 56 58 60 62 64 66 68 70 72 74 76
[ Wet bulb temperature of air entering indoor coil ]
Model -18 -24 -30 -36 -42 -48 -60
Table 3. Normal Operating Pressures
1
°F(°C)
2
TXV System - Liquid Line (+10 psig) / Vapor Line (+5 psig)
65 (18) 233 / 132 244 / 137 248 / 127 263 / 135 250 / 135 240 / 130 242 / 130
70 (21) 251 / 133 263 / 138 263 / 131 281 / 138 268 / 137 257 / 131 266 / 131
75 (24) 265 / 133 285 / 139 284 / 132 302 / 140 288 / 138 278 / 132 286 / 132
80 (27) 292 / 135 307 / 140 307 / 134 325 / 142 310 / 139 299 / 133 309 / 133
85 (29) 314 / 136 329 / 141 330 / 135 349 / 142 332 / 140 323 / 134 332 / 134
90 (32) 338 / 137 354 / 142 355 / 136 375 / 143 356 / 140 344 / 135 357 / 135
95 (35) 362 / 138 379 / 143 380 / 137 404 / 144 381 / 141 369 / 136 381 / 136
100 (38) 388 / 140 404 / 144 407 / 138 433 / 145 406 / 143 394 / 137 407 / 137
105 (41) 415 / 141 438 / 145 434 / 139 462 / 147 432 / 143 418 / 139 433 / 138
110 (43) 444 / 142 464 / 147 465 / 141 494 / 149 459 / 145 446 / 140 459 / 140
115 (45) 475 / 143 495 / 148 497 / 142 527 / 150 490 / 145 477 / 141 488 / 141
°F(°C)
2
Fixed Orifice (RFC) - Liquid Line (+10 psig) / Vapor Line (+5 psig)
65 (18) 233 / 121 246 / 126 245 / 123 261 / 134 250 / 135 248 / 127 255 / 126
70 (21) 250 / 124 265 / 129 265 / 126 281 / 136 268 / 137 266 / 130 274 / 128
75 (24) 270 / 128 286 / 132 286 / 129 301 / 138 288 / 138 284 / 132 294 / 131
80 (27) 291 / 131 307 /135 308 / 132 324 / 140 310 / 139 305 / 134 317 / 134
85 (29) 313 / 134 330 / 137 331 / 135 346 / 142 332 / 140 325 / 137 339 / 136
90 (32) 335 / 136 353 / 140 355 / 138 371 / 144 356 / 140 347 / 139 362 / 138
95 (35) 359 / 138 378 / 142 380 / 140 396 / 146 381 / 141 371 / 141 386 / 140
100 (38) 383 / 140 402 / 143 405 / 142 422 / 148 406 / 143 394 / 143 413 / 142
105 (41) 409 / 142 428 / 145 431 / 144 448 / 150 432 / 143 418 / 144 435 / 144
110 (43) 436 / 145 456 / 147 458 / 146 477 / 151 459 / 145 445 / 146 462 / 146
115 (46) 464 / 147 486 / 149 487 / 148 506 / 153 490 / 145 472 / 147 490 / 148
Table 4. Approach (APP) Values
3
- TXV System - ºF (ºC) +1ºF (0.5ºC)
All 4 (2.2) 8 (4.4) 8 (4.4) 11 (6.1) 10 (5.6) 6 (3.3) 9 (5.0)
Table 5. Subcooling (SC) Values
4
- TXV System - ºF (ºC) +1ºF (0.5ºC)
All 10 (5.6) 10 (5.6) 9 (5.0) 12 (6.7) 8 (4.4) 10 (5.6) 7 (3.9)
1 Typical pressures; indoor evaporator match up, indoor air quantity, and evaporator load will cause
the pressures to vary.
2 Temperature of air entering outside coil.
3 Approach = Liquid Line Temp. minus Outdoor Ambient Temperature
4 Subcooling = Saturation Temp. minus Liquid Line Temp Temperature
*2P1107* *P401288S*
11/07 401288S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox 14ACX and is the answer not in the manual?

Lennox 14ACX Specifications

General IconGeneral
Compressor TypeSingle-stage
Cooling Capacity (BTU/h)18, 000 to 60, 000
RefrigerantR-410A
Energy Star CertifiedNo
Voltage208/230V
Phase1
Unit WeightVaries by model
Dimensions (H x W x D)Varies by model
SEER Rating14
Cooling Capacity1.5 to 5 tons
Sound Level (dBA)76

Related product manuals