Electrical Data
208/230V-60 Hz-1 Ph
Model Numbers Label Rev.
Unit Compressor Condenser Fan
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated
Load
Amps
(RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps
(FLA)
Locked
Rotor
Amps
(LRA)
14ACX-018-230-01 1.0 20 12.3 9.0 48.0 1/5 1075 1.1 2.0
14ACX-024-230-02
1.0 20 12.3 9.0 58.3 1/5 1075 1.1 2.0
2.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.4
14ACX-018-230-10 1.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.4
14ACX-018-230-11 1.0 & 2.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.4
14ACX-018-230-12
1.0 & 2.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.3
3.0 20 12.4 9.0 48.0 1/10 1075 0.7 1.3
4.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.3
14ACX-018-230-13
1.0 20 12.4 9.0 48.0 1/10 1075 0.7 1.3
2.0 20 12.0 9.0 48.0 1/10 1075 0.7 1.3
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
208/230V-60 Hz-1 Ph
Model Numbers Label Rev.
Unit Compressor Condenser Fan
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated
Load
Amps
(RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps
(FLA)
Locked
Rotor
Amps
(LRA)
14ACX-024-230-01 1.0 30 17.9 13.4 58.3 1/5 1075 1.1 2.0
14ACX-024-230-02 1.0 30 17.9 13.4 58.3 1/5 1075 1.1 2.0
14ACX-024-230-10 1.0 & 2.0 30 17.9 13.4 58.3 1/6 1075 1.1 1.9
14ACX-024-230-11 1.0 & 2.0 30 17.9 13.4 58.3 1/6 1075 1.1 1.9
14ACX-024-230-12 1.0 & 2.0 30 17.9 13.4 58.3 1/6 1075 1.1 1.9
14ACX-024-230-16
1.0 30 17.9 13.4 58.0 1/6 1075 1.1 1.9
2.0 30 17.9 13.46 58.0 1/6 1075 1.1 1.9
3.0 30 17.8 13.46 58.0 1/6 825 1.0 1.9
14ACX-024-230-17
1.0 30 18.7 13.4 58.0 1/6 825 1.9 1.9
2.0 30 17.8 13.4 58.0 1/6 825 1.0 1.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
208/230V-60 Hz-1 Ph
Model Numbers Label Rev.
Unit Compressor Condenser Fan
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated
Load
Amps
(RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps
(FLA)
Locked
Rotor
Amps
(LRA)
14ACX-030-230-01 1.0 30 17.2 12.9 64.0 1/6 825 1.1 2.1
14ACX-030-230-02 1.0 30 17.2 12.9 64.0 1/6 825 1.1 2.1
14ACX-030-230-10 1.0 & 2.0 30 17.2 12.9 64.0 1/6 825 1.1 2.1
14ACX-030-230-11 1.0 & 2.0 30 17.2 12.9 64.0 1/6 825 1.1 2.1
14ACX-030-230-12
1.0 & 2.0 30 17.2 12.9 64.0 1/6 825 1.1 2.1
3.0 25 17.1 12.9 64.0 1/6 825 1.0 2.1
14ACX-030-230-13 1.0 25 17.1 12.9 64.0 1/6 825 1.0 1.9
14ACX-030-230-15 1.0 25 17.1 12.9 64.0 1/6 825 1.0 1.9
14ACX-030-230-16 1.0 25 17.1 12.9 64.0 1/6 825 1.0 1.9
14ACX-030-230-17 1.0 25 17.1 12.9 64.0 1/6 825 1.0 1.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.