Field wiring must comply with codes; follow safety warnings for line voltage and grounding.
Procedures for brazing connections, using nitrogen purge, and selecting metering devices (fixed orifice or TXV).
Provides data for fixed orifices and shows how to install metering devices (fixed orifice or TXV) into the indoor coil.
Details on selecting and installing expansion valves (TXV) and using manifold gauge sets.
Procedures for leak testing with nitrogen and evacuating the system using a vacuum pump to remove noncondensables.
Detailed steps for evacuating the system to a minimum of 500 microns using a vacuum pump and micron gauge.
Rotate fan, inspect wiring, check voltage, and ensure crankcase heater is energized if applicable.
Procedures for charging the system with HCFC-22 refrigerant based on line set diameter and weather conditions.
Explains weigh-in, subcooling, superheat, and approach methods for refrigerant charging.
Turn off power before maintenance. Electrical shock hazard is present.