THERMOSTAT – Set point calculate
Function
Set the chilled or hot water circuit temperature, depending on the outdoor conditions in order to optimise the
energy consumption.
Description
Calculation of the chilled water set point :
Calculation of the chilled water set point:
²
Outdoor
Temperature
3321
10°C
3322
7°C
Values are given for indications only.
Gradient can be positive or negative.
Values are given for indications only.
Gradient can be positive or negative.
3323
22°C
3324
30°C
Calculated
Set Point
Calculated
Set Point
3331
40°C
3332
30°C
3334
0°C
3333
19°C
Outdoor
Temperature