CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
39
FAULT CODES
FAN(S) CIRCUIT BREAKER(S) OPEN
Fault Code: 90, 92, 93, 94, 95
Description
One or more thermal magnetic trip circuit breaker protecting the condenser fans are tripped
Ecologic unit ! Fault code 90
Ecomax unit circuit 1 ! code 92
Ecomax unit circuit 2 ! code 93
Ecomax unit circuit 3
!
code 94
Ecomax unit circuit 4 ! code 95
Reset
The fault is cleared automatically as soon as the fans circuit breakers are closed
Possible causes Solving the problem
Wrong wiring or tightening of the connections. Control all connections
Wrong setting on the circuit breaker
Set circuit breaker according with compressor
normal running current