CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
64
BM 50 address configuration
It may be necessary to change BM50 addresses on the LAN network - mainly in case of Master / Slave
installation. Follow the procedure hereunder to do so:
1. Change the DS50 address to 0
- Turn the power OFF/ON on the BM50, then access the configuration mode by pressing !"# for at least 5
seconds until you reach the following screen:
Display address
Setting..........:32
I/O Board address:--
Display address
Setting..........:32
I/O Board address:--
By using ! " keys Change the Display addresses setting to 0 (instead of 32 as standard value) and
validate with # key.
2. Change the BM50 address
Shut off the power on the BM50 and then turn it on again after 5 seconds, then press alarm and !keys in
order to get the following screen
Then you will get:
pLan addresse: 0
UP: increase
DOWN: decrease
ENTER: save & exit
pLan addresse: 0
UP: increase
DOWN: decrease
ENTER: save & exit
By using ! " keys Change the pLan address to the correct value (1 to 4) and validate with # key.
####################
self test
please wait...
####################
####################
self test
please wait...
####################
Select
Select