05/09 506230−01
*2P0509* *P506230-01*
Available System Settings
Setup HEAT PUMP Configurations NON HEAT PUMP Configurations
Backup/ In-
door Heat
Gas/Oil Gas/Oil None Gas/Oil Gas/Oil None Elec Elec None Elec Elec None G/O or
Elec
G/O or
Elec
None G/O or
Elec
G/O or
Elec
None
Comp.
Stages
1 1 1 2 2 2 1 1 1 2 2 2 1 1 1 2 2 2
Indoor Heat
Stgs
1 2 0 1 2 0 1 2 0 1 2 0 1 2 0 1 2 0
Total Heat
Stgs
2 3 1 3 4 2 2 3 1 3 4 2 1 2 0 1 2 0
1st Heat
Stage
Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 W1 W1 W1 W1
2nd Heat
Stage
W1 W1 Y1+Y2 Y1+Y2 Y1+Y2 Y1+W1 Y1+W1 Y1+Y2 Y1+Y2 Y1+Y2 W1+W2 W1+W2
3rd Heat
Stage
W1+W2 W1 W1 Y1+W1+
W2
Y1+Y2+
W1
Y1+Y2+
W1
4th Heat
Stage
W1+W2 Y1+Y2+
W1+W2
1st Em Heat
Stage
W1 W1 W1 W1 W1 W1 W1 W1
2nd Em heat
Stage
W1+W2 W1+W2 W1+W2 W1+W2
Cool Stages 1 1 1 2 2 2 1 1 1 2 2 2 1 1 1 2 2 2
1st Cool
Stage
Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
2nd Cool
Stage
Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2 Y1+Y2
Indoor Heat
Stgs
X X X X X X X X X X X X
Outdoor
Sensor
X X X X X X X X X X X X X X X X X X
Residual
Cool
X X X X X X X X X X X X X X X X X X
Low Balance
Pt.
X X X X X X X X
High Bal-
ance Pt.
X X X X X X X X
Stg Delay
Timers
X X X X X X X X X X X X X X
Stg 1 Diff X X X X X X X X X X X X X X X X X X
Stg 2 Diff X X X X X X X X X X X X X X
Stg 2 Delay X X X X X X X X X X X X X X
Stg 3 Diff X X X X X X
Stg 3 Delay X X X X X X
Stg 4 Diff X X
Stg 4 Delay X X
H/C Stgs
Locked In
X X X X X X X X X X X X X
Stg 2 Hp
Lock Temp
X X X X
Humiditrol
Adjust
If Dehumidification mode is not equal to HUMIDITROL.
LEGEND
FILLED−IN CELL INDICATES SELECTION IS NOT AVAILABLE (IS HIDDEN) FOR THE SPECIFIC CONFIGURATION