31
Action to Clear /
Recovery Condition
System ActionCondition
Message
Type
Priority
0:high
1:middle
2:low
Screen Text
Error
Code
10
humidity
sensor error
1 critical
With humidifier or dehu
midifier) and conditions are
as follows:
0%: Stat will detect error
0-5%: Stat may detect
error
5-95%: Normal operation
95-99%: Thermostat may
detect error
100%: Thermostat will
detect error
All humidity operation will stop
and the reading for humidity
will not be valid.
This message indicates hum
sensor is not working correctly.
The display of Indoor Humidity
on HOME screen will be "--".
This error is displayed in notifi
cation screen.
Either thermostat will
have to be replace or if
the sensor returns to
normal operating range,
the error message will
automatically clear and
the system will resume
operation.
11
humidity
sensor error
1 critical
Without humidifier or de
humidifier and the sensor
reads out of range 0% to
100%.
The reading for humidity will
not be valid.
This message indicates hum
sensor is not working correctly.
The display of Indoor Humidity
on HOME screen will be "--".
This error is displayed in notifi
cation screen.
19
Economiz
er fault
0 critical
F terminal receives
24VAC and error will be
displayed
User can contact the dealer or move this error to the
notification screen.