11/08 505103M
*2P1108* *P505103M*
COMMERCIAL
CONTROLS
505103M
11/08
Supersedes 01/2007
INSTALLATION
INSTRUCTIONS
Commercial
Touch
Screen
Thermostat
E2008 Lennox Industries Inc.
Dallas, Texas, USA
Application
The Lennox Commercial Touchscreen Thermo-
stat provides electronic control of 24 Vac heating
and cooling systems. See Table 1 for a descrip-
tion.
Table 1. Thermostat Description
Feature Description
Powering
Methods
S Battery only
S Direction connection to a 24 Vac
transformer only.
S Direct connection to a 24 Vac
transformer with battery backup.
System
Types
S Conventional (up to 2 heat, 2 cool
stages)
S Heat Pump (up to 3 heat, 2 cool
stages)
Changeover Manual or automatic changeover (se-
lectable)
System Set-
tings
Heat−Off−Cool−Auto
Fan Settings Auto−on
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old con-
trol in the trash. Dispose of properly.
Contact your local waste management authority for
instructions regarding recycling and the proper dis-
posal of an old control.
Installation
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or
cause a hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for
your application.
3. Installer must be a trained, experienced ser-
vice technician.
4. After installation is complete, check out prod-
uct operation as provided in these instruc-
tions.
CAUTION
Electrical Shock or Equipment Damage haz-
ard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Select Thermostat Location
Select a location for the thermostat about 5 feet
(1.5m) above the floor in an area with good air cir-
culation at average temperature (see figure 1).
YES
NO
NO
NO
5 FEET
(1.5 METERS)
Figure 1. Select Thermostat Location
Do not install the thermostat where it can be af-
fected by:
D Drafts or dead spots behind doors and in
corners.
D Hot or cold air from ducts.
D Radiant heat from sun or appliances.
D Concealed pipes and chimneys.
D Unheated (uncooled) areas such as an
outside wall behind the thermostat.

Other manuals for Lennox Commercial Touchscreen Thermostat

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Commercial Touchscreen Thermostat and is the answer not in the manual?

Lennox Commercial Touchscreen Thermostat Specifications

General IconGeneral
BrandLennox
ModelCommercial Touchscreen Thermostat
CategoryThermostat
LanguageEnglish

Related product manuals