Page 11
EL16XC1 SERIES
STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han
dler for low‐voltage control power (24VAC - 40 VA mini
mum)
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be properly grounded
in accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
IMPORTANT !
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
WARNING
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this product.
CAUTION
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specifications bulletin (EHB) and
unit rating plate.
CAUTION
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
Electrostatic discharge can affect
electroniccomponents.Takecareduring
unit installation and service to protect the
unit's electronic controls. Precautions
will help to avoid control exposure to
electrostatic discharge by putting the
unit, the control and the technician at the
same electrostatic potential. Touch hand
and all tools on an unpainted unit surface
beforeperforminganyserviceprocedure
to neutralize electrostatic charge.
Refer to the unit nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker (HACR per NEC). Install power wiring and properly
sized disconnect switch.
NOTE - Units are approved for use only with copper conductors.
Ground unit at disconnect switch or connect to an earth ground.
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
NOTE - 24VAC, Class II circuit connections are made in the control
panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m)
from the floor. It should not be installed on an outside wall or where it
can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
DISCONNECT
SWITCH
MAIN FUSE
BOX/BREAKER
PANEL
FIGURE 11