Page 14
HORIZONTAL RIGHT POSITION
Top Vent Discharge
  Gas supply piping must be brought into the unit from the bottom
in order to accommodate the flue pipe.
Remove make-up box assembly (2 screws) and cut wire tie to
free make-up box wires. Re-install make-up box on other side
of cabinet.
 
Re-secure make-up box wires by either pulling excess wires
through the blower compartment and securing with supplied
wire tie, or coil excess wire and secure to the gas manifold.
FLOW
AIR
flue transition
vent pipe
pressure switch
cover plate
make-up box
collector box
Figure 20 
HORIZONTAL RIGHT POSITION
Side Vent Discharge - no modifications necessary
FLOW
AIR
Pressure Switch
Flue Transition
Collector Box
Make-Up Box
Vent Pipe
Figure 21 
The EL180UHE series units are classied as fan-assisted 
Category I furnaces when vertically vented according to 
the latest edition of National Fuel Gas Code (NFPA 54 / 
ANSI Z223.1) in the USA. 
A fan-assisted Category I furnace is an appliance equipped 
with an integral mechanical means to either draw or force 
combustion products through the combustion chamber 
and/or heat exchanger. The EL180UHE is not approved 
for use with horizontal venting.
NOTE - Use these instructions as a guide. They do not su-
persed local codes. This funace must be vented according 
to all locawl codes these installation instructions, and the 
provided venting tables in these instructions
The venting tables in this manual were extracted from the 
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are 
provided as a guide for proper vent installation. Proper 
application, termination, construction and location of vents 
must conform to local codes having jurisdiction. In the ab-
sence  of  local  codes,  the  NFGC  serves  as  the  dening 
document.
Use self-drilling sheet metal screws or a mechanical fas-
tener to rmly secure the vent pipe to the round collar of 
the ue transition. If self-drilling screws are used to attach 
the vent pipe, it is recommended that three be used. Drive 
one self-drilling screw through the front and one through 
each side of the vent pipe and collar. See gure 22.
Install the rst vent connector elbow at a minimum of six 
inches (152 mm) from the furnace vent outlet. See gure 
22.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined 
masonry chimney is used to vent this furnace. Masonry 
chimneys used to vent Category I central furnaces must 
be either tile-lined or lined with a listed metal lining sys-
tem or dedicated gas vent. Unlined masonry chimneys are 
prohibited. See gures 23 and 24 for common venting.
A chimney with one or more sides exposed to the outside 
of the structure is considered to be an exterior chimney. 
An exterior masonry chimney that is not tile-lined must be 
lined with B1 vent or a listed insulated exible metal vent. 
An exterior tile-lined chimney that is sealed and capped 
may be lined with a listed uninsulated exible metal vent. 
If the existing chimney will not accommodate a listed met-
al liner, either the chimney must be rebuilt to accommo-
date one of these liners or an alternate approved venting 
method must be found.
Insulation for the exible vent pipe must be an encapsu-
lated berglass sleeve recommended by the exible vent 
pipe manufacturer. See gure 23.
Refer to the tables and the venting information contained 
in these instructions to properly size and install the venting 
system.
 IMPORTANT
Once the venting system is installed, attach the 
“Disconnected Vent” warning sticker to a visible area 
of the plenum near the vent pipe. See gure 22. The 
warning sticker is provided in the bag assembly. Order 
kit 66W04 for additional stickers..