Page 16
Joint Cementing Procedure
All cementing of joints should be done according to the 
specications outlined in ASTM D 2855.
NOTE - A sheet metal screw may be used to secure the 
intake pipe to the connector, if desired. Use a drill or self 
tapping screw to make a pilot hole.
 DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. 
Allow fumes to dissipate for at least 5 minutes before 
placing unit into operation.
1 -   Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges 
or rough edges. If end is not chamfered, edge of pipe 
may remove cement from tting socket and result in a 
leaking joint.
NOTE - Check the inside of vent pipe thoroughly for 
any obstruction that may alter furnace operation.
3 -  Clean and dry surfaces to be joined.
4 -  Test t  joint and mark depth of  tting on outside of 
pipe.
5 -  Uniformly apply a liberal coat of PVC primer for PVC 
or use a clean dry cloth for ABS to clean inside socket 
surface  of  tting  and  male  end  of  pipe  to  depth  of 
tting socket.
6 -  Promptly apply solvent cement to end of pipe and 
inside  socket  surface  of  tting.  Cement  should  be 
applied lightly but uniformly to inside of socket. Take 
care to keep excess cement out of socket. Apply 
second  coat to end of pipe.
NOTE - Time is  critical at this  stage. Do  not allow 
primer to dry before applying cement.
7 -  Immediately after applying last coat of cement to 
pipe, and while both inside socket surface and end 
of pipe are wet with cement, forcefully insert end of 
pipe into socket until it bottoms out. Turn PVC pipe 
1/4 turn during assembly (but not after pipe is fully 
inserted) to distribute cement evenly. DO NOT turn 
ABS or cellular core pipe.
NOTE - Assembly  should  be  completed  within  20 
seconds  after  last  application  of  cement.  Hammer 
blows should not be used when inserting pipe.
8 -  After assembly, wipe excess cement from pipe at 
end of tting socket. A properly made joint will show 
a bead around its entire perimeter. Any gaps may 
indicate  an  improper  assembly  due  to  insucient 
solvent.
9 -  Handle joints carefully until completely set.
Venting Practices
* See  Piping and Fittings Specifications table
Piping Suspension Guidelines
NOTE - Isolate piping at the point where it exits the outside wall o
roof in order to prevent transmission of vibration to the structure.
SCHEDULE 40
PVC - 5'
all other pipe*  - 3'
Wall
edistuoedisni
24” maximum
3/4” minimum
Wall Thickness Guidelines
FIGURE 24 
If replacing a furnace which was
commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without  the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the  single  water  heater  or  other  appliance.  The  vent
should be checked for proper draw with the remaining
appliance.
REPLACING FURNACE THAT WAS PART OF A
COMMON VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced)
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 25 
1 -   In areas where piping penetrates joists or interior 
walls, hole must be large enough to allow clearance 
on all sides of pipe through center of hole using a 
hanger.