Page 4
Building Codes
In the USA, installation of gas furnaces must conform with 
local building codes. In the absence of local codes, units 
must be installed according to the current National Fuel 
Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel 
Gas Code is available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National 
Standard of Canada CSA-B149 Natural Gas and Propane 
Installation Codes, local plumbing or waste water codes 
and other applicable local codes.
In order to ensure proper unit operation in non-direct vent 
applications, combustion and ventilation air supply must 
be provided according to the current National Fuel Gas 
Code or CSA-B149 standard.
Locations and Clearances
This furnace is CSA International certied for installation 
clearances to combustible material as listed on the unit 
nameplate and in the table in FIGURE 13. Accessibility 
and  service  clearances  must  take  precedence  over  re 
protection clearances.
For installation in a residential garage, the furnace must 
be installed so that the burner(s) and the ignition source 
are located no less than 18 inches (457 mm) above the 
oor. The furnace  must be located or  protected to avoid 
physical damage by vehicles. When a furnace is installed 
in a public garage, hangar, or other building that has a 
hazardous atmosphere, the furnace must be installed ac-
cording to recommended good practice requirements and 
current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature 
rise within the range specied on the unit nameplate. Fail-
ure to do so may cause erratic limit operation and prema-
ture heat exchanger failure.
This EL296DFE furnace must be installed so that its elec-
trical components are protected from water.
Installation in Combination with a Cooling Coil
When this furnace is used with cooling units (FIGURE 3), 
it shall be installed in parallel with, or on the upstream 
side of, cooling units to avoid condensation in the heating 
compartment. With a parallel ow arrangement, a damper 
(or other means to control the ow of air) must adequately 
prevent chilled air from entering the furnace. If the damper 
is manually operated, it must be equipped to prevent op-
eration of either the heating or the cooling unit, unless it is 
in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded 
according to local codes. In addition, in the United States, 
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code 
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit 
must be installed according to the current regulations of 
the Canadian Electrical Code Part I (CSA Standard C22.1) 
and/or local codes.
 
AIR HANDLER
GAS UNIT
Dampers
(open during cooling
operation only)
Dampers
(open during heating
operation only)
FIGURE 3 
NOTE - This furnace is designed for a minimum continu-
ous return air temperature of 60°F (16°C) or an intermittent 
operation down to 55°F (13°C) dry bulb for cases where a 
night setback thermostat is used. Return air temperature 
must not exceed 85°F (29°C) dry bulb.
The EL296DFE furnace may be installed in alcoves, clos-
ets, attics, basements, garages, utility rooms and crawl 
spaces.
This furnace design has not been CSA certied for instal-
lation in mobile homes, recreational vehicles, or outdoors.
Never use an open ame to test for gas leaks. Check all 
connections using a commercially available soap solution 
made specically for leak detection.
Use of Furnace as Construction Heater
Units may be used for heating of buildings or structures 
under construction, if the following conditions are met to 
ensure proper operation:
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT 
UNLESS ALL OF THE FOLLOWING CRITERIA ARE 
MET:
•   Furnace must be in  its nal location. The vent system 
must be permanently installed per these installation in-
structions.
•    Furnace must be installed as a two pipe system and 
one hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion.
•    A room thermostat must control the furnace. The use 
of xed jumpers that will provide continuous heating is 
prohibited.
•   The input rate and temperature rise must be set per the 
furnace rating plate. 
•    Supply and Return air ducts must be provided and 
sealed to the furnace. Return air must be terminated 
outside of the space where furnace is installed.