Page 50
Other Unit Adjustments
NOTE - See  troubleshooting  ow  charts  if  any  safety 
switches are found to be open.
Primary Limit
The primary limit is located on the heating compartment 
vestibule panel. This limit is factory set and requires no 
adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of 
the burner box.
Pressure Switch
The pressure switch is located in the heating compartment 
on the cold end header box. This switch checks for proper  
combustion air inducer operation before allowing ignition 
trial. The switch is factory-set and must not be adjusted.
Temperature Rise
Place the unit into operation with a second-stage heating 
demand. After supply and return air temperatures have 
stabilized, check the temperature rise. If necessary, adjust 
the heating blower speed to maintain the temperature rise 
within the range shown on the unit nameplate. See TABLE 
20 on page 59 for allowable heating speeds.Increase 
the blower speed to decrease the temperature rise. De-
crease the blower speed to increase the temperature rise. 
Failure to properly adjust the temperature rise may cause 
erratic limit operation.
Electrical
1 -   Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace 
operating). Correct voltage is 120VAC + 10%
3 - Check amp-draw on the blower motor with blower 
access panel in place.
Motor Nameplate__________Actual__________
Exhaust and Air Intake Pipe
1 -   Check exhaust and air intake connections for 
tightness and to make sure there is no blockage.
2 -  Is pressure switch closed? Obstructed exhaust pipe 
will cause unit to shut o at pressure switch. Check 
termination for blockages.
3 -  Obstructed pipe or termination may cause rollout 
switches to open. Reset manual ame rollout
Heating Sequence of Operation
Electronic Ignition
The two-stage, variable speed integrated control used 
in EL296DFE units has an added feature of an internal 
Watchguard control. The feature serves as an automatic 
reset device for ignition control lockout caused by ignition 
failure. After one hour of continuous thermostat demand 
for heat, the Watchguard will break and remake thermo-
stat demand to the furnace and automatically reset the 
control to begin the ignition sequence.
NOTE - The  ignition  control  thermostat  selection  DIP 
switch is factory-set in the “TWO-STAGE” position.
Applications Using a Two-Stage Thermostat
A - Heating Sequence -- Integrated Control Thermo-
stat Selection DIP Switch 1 OFF in “Two-Stage” Posi-
tion (Factory Setting)
1 -   On  a  call  for  heat,  thermostat  rst-stage  contacts 
close sending a signal to the integrated control. The 
integrated control runs a self-diagnostic program 
and checks high temperature limit switches for 
normally closed contacts and pressure switches for 
normally open contacts. The combustion air inducer 
is energized at low speed.
2 -  Once the control receives a signal that the low 
pressure switch has closed, the combustion air 
inducer begins a 15-second pre-purge in low speed.
NOTE - If the low re pressure switch does not close 
the  combustion  air  inducer  will  switch  to  high  re. 
After a 15 second pre-purge the high re pressure 
switch will close and the unit will begin operation on 
high re. After 10 to 20 seconds of high re opera-
tion the unit will switch to low re..
3 -  After the pre-purge is complete, a 20-second initial 
ignitor warm-up period begins. The combustion air 
inducer continues to operate at low speed.
4  -   After the 20-second warm-up period has ended, the 
gas  valve  is  energized  on low  re  (rst  stage)  and 
ignition occurs.  At the same time, the control module 
sends a signal to begin an indoor blower 30-second 
ON-delay. When the delay ends, the indoor blower 
motor is energized on the low re heating speed, the 
HUM  contacts  close  energizing  the  humidier  and 
120V ACC terminal is energized. The furnace will 
continue this operation as long as the thermostat has 
a rst-stage heating demand.
5 -  If second-stage heat is required, the thermostat 
second- stage heat contacts close and send a signal 
to the integrated control. The integrated control 
initiates a 30-second second-stage recognition 
delay.
6 -  At the end of the recognition delay, the integrated 
control energizes the combustion air inducer at high 
speed. The control also checks the high re (second 
stage) pressure switch to make sure it is closed. The 
high re (second stage) gas valve is energized and 
the indoor blower motor is energized for operation at 
the high re heating speed.
7 -  When the demand for high re (second stage) heat 
is satised, the combustion air inducer is switched to 
the low-re heating speed and the high-re (second 
stage) gas valve is  de-energized. The low-re (rst 
stage) gas valve continues operation. The indoor 
blower  motor  is  switched  to  the  low-re  heating 
speed.
8 -  When the thermostat demand for low-re (rst stage) 
heat is satised, the gas valve is de-energized and 
the  eld-selected  indoor  blower  o  delay  begins. 
The combustion air inducer begins a 5-second post-
purge period.
9 -  When the combustion air post-purge period is com-
plete, the inducer and the HUM contacts are de-ener-
gized. The indoor blower is de-energized at the end of 
the o delay as well as the 120V ACC terminal.