Page 35
Gas Piping
 CAUTION
If a exible gas connector is required or allowed by the 
authority that has jurisdiction, black iron pipe shall be 
installed at the gas valve and extend outside the furnace 
cabinet.  The  exible  connector  can  then  be  added 
between the black iron pipe and the gas supply line.
 WARNING
Do not over torque (800 in-lbs) or under torque (350 in-
lbs) when attaching the gas piping to the gas valve.
1 -   Gas piping may be routed into the unit through either 
the left- or right-hand side. Supply piping enters into 
the gas valve from the side of the valve as shown in 
FIGURE 56. Connect the gas supply piping into the 
gas valve. The maximum torque is 800 in lbs and 
minimum torque is 350 in lbs when when attaching 
the gas piping to the gas valve.
2 -  When connecting gas supply, factors such as length 
of  run,  number  of  ttings  and  furnace  rating  must 
be considered to avoid excessive pressure drop. 
TABLE 11 lists recommended pipe sizes for typical 
applications.
NOTE - Use  two  wrenches  when  connecting  gas 
piping to avoid transferring torque to the manifold.
3 -  Gas piping must not run in or through air ducts, 
clothes chutes, chimneys or gas vents, dumb waiters 
or elevator shafts. Center gas line through piping 
hole. Gas line should not touch side of unit. See 
FIGURE 56.
4 -  Piping should be sloped 1/4 inch per 15 feet (6mm 
per 5.6m) upward toward the gas meter from the 
furnace. The piping must be supported at proper 
intervals, every 8 to 10 feet (2.44 to 3.05m), using 
suitable hangers or straps. Install a drip leg in 
vertical pipe runs to serve as a trap for sediment or 
condensate.
5 -  A 1/8” N.P.T. plugged tap or pressure post is located 
on the gas valve to facilitate test gauge connection. 
See FIGURE 60.
6 - In some localities, codes may require installation of 
a  manual  main  shut-o  valve  and  union  (furnished 
by installer) external to the unit. Union must be of the 
ground joint type.
 IMPORTANT
Compounds used on threaded joints of gas piping must 
be resistant to the actions of liquied petroleum gases.
Leak Check
After gas piping is completed, carefully check all piping 
connections  (factory-  and  eld-installed)  for  gas  leaks. 
Use a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system 
by closing its individual manual shut-o valve during any 
pressure  testing  of  the  gas  supply  system  at  pressures 
less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8” N.P. T. PLUGGED TAP
FIGURE 55 
 IMPORTANT
When testing pressure of gas lines, gas valve must be 
disconnected and isolated. See FIGURE 55. Gas valves 
can be damaged if subjected to pressures greater than 
1/2 psig (3.48 kPa).
 WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result 
in serious injury, death, or property damage. Never use 
an open ame to test for gas leaks. Check all connections 
using a commercially available soap solution made 
specically for leak detection. Some soaps used for leak 
detection are corrosive to certain metals. Carefully rinse 
piping thoroughly after leak test has been completed.