EasyManua.ls Logo

Lennox ELITE 12GCS Series

Lennox ELITE 12GCS Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 9
I−APPLICATION
12GCS 2 through 5 ton (7.0 through 17.6kW) model units
are single packaged heat/cool units designed for outdoor
installation on a slab or rooftop.The units are available in
three cabinet sizes. 12CHP 2 through 5 ton (7.0 through
17.6kW) model units are available in three cabinet sizes and
are designed for outdoor installation on a slab or rooftop.
Electric heat can be factory or field installed if required.
12GCS/12CHP units are single−phase and residential only.
Refer to the Engineering Handbook for more specific ap-
plication data.
II−UNIT COMPONENTS
12GCS components are shown in figure 1. 12CHP compo-
nents are in figure 2. Component description will be broken
down into three categories: Control box, Gas and Cooling.
Some control box and cooling components will be shared by
both 12GCSmodel units and 12CHP model units. These com-
ponents will be identified as all models . Other components
will be identified as either GCS only" or CHP only"
A−Control Box Components
12GCS control box components are shown in figure 3. 12CHP
control box components are shown in figure 4.
1−Compressor Contactor K1 (all models)
K1 is a 24VAC to line voltage two pole double break contactor,
which energizes the compressor and condenser fan in re-
sponse to thermostat demand.
2−Control Transformer T1 (all models)
All 12GCS/12CHP series units use line voltage to 24VAC
transformer mounted in the control box. The transformer sup-
plies power to control circuits in the unit. Transformers use two
primary voltage taps as shown in figure 5.
FIGURE 5
240 VOLTS
208 VOLTS
PRIMARY
SECONDARY
208 / 240 VOLT TRANSFORMER
24 VOLTS
L1
L2
3−Dual Capacitor C12 (all models)
The compressor and condenser fan in the 12GCS/12CHP se-
ries units use permanent split capacitor motors. The capacitor
is located in the control box. A dual rated capacitor is used for
both the condenser fan motor and the compressor (see unit
wiring diagram per respective unit). The fan side and the com-
pressor side of the capacitor have different MFD ratings. See
side of capacitor for ratings.
4−Ignition/Blower Control A3 (GCS only)
All 12GCS series units are equipped with an integrated ignition
/ blower board (A3) which controls ignition, safety circuits,
blower operation and fan off timing. See figure 6. Table 1
shows jack plug terminal designations.
Ignition control
All 12GCS units use direct spark ignition which is controlled by
an integrated ignition control board. On a call for heat the con-
trol monitors the combustion air prove switch. The control will
not begin the heating cycle if the prove switch is closed (by−
passed). Once the prove switch is determined to be open, the
combustion air inducer blower is energized. When the differen-
tial in the prove switch is great enough, the switch closes and a
30−second pre−purge begins. After the pre−purge period, the
gas valve opens and ignition (spark) is attempted for 10 sec-
onds. If the initial attempt for ignition fails, the sequence is re-
peated two more times. After a total of three failed attempts,
the board goes into Watchguard. During watchguard mode,
the board is de−energized for one hour. After one hour the con-
trol will repeat the ignition sequence. Watchguard may be
manually reset by breaking and remaking thermostat demand.
FIGURE 6
THERMOSTAT
CONNECTIONS
6 PIN PLUG 24VAC
LED DIAGNOSTIC
CONDITIONS
SPARK IGNITION
1
3
2
4
5
6
12GCS INTEGRATED CONTROL
BLOWER SPEED
TERMINALS
Safety Circuits
During the heating cycle the control monitors the safety circuits.
If the primary or secondary heating limits open, the control de−
energizes the gas valve and combustion air inducer blower
while the indoor blower remains energized. When the limit au-
tomatically resets the ignition sequence also resets.
If the rollout switch opens, the control de−energizes the gas
valve and the combustion air inducer blower. The unit will re-
main de−energized until the rollout switch is manually reset.

Related product manuals