Page 13
*Gas connector may be
used  for  Canadian
able  by  local  authority
having jurisdiction.
*GAS CONNECTION
RAISED
PLATFORM
SERVICE PLATFORM
INTAKE PIPE
EXHAUST PIPE
Figure 19 
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a 
furnace installed in the horizontal position. The furnace is 
equipped with a removable bottom panel to facilitate in-
stallation. See Figure 15.
Filters
-
          
 IMPORTANT
       
and performance may be reduced.
The pressure drop may also cause the limit to trip more 
frequently during the winter and the indoor coil to freeze 
in the summer, resulting in an increase in the number of 
service calls.
        
the data given in the appropriate Lennox Product 
in Service and Application Note ACC002
(August 2000).
TABLE 1 
Furnace
Cabinet Width
Filter Size
Side Return Bottom Return
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24-1/2” 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Duct System
Use industry-approved standards to size and install the 
supply and return air duct system. Refer to ACCA Manual 
D. This will result in a quiet and low-static system that has 
uniform air distribution. See below for proper duct instal-
lation.
HORIZONTAL UNIT
SUPPLY
AIR
SUPPLY
AIR
Install self tapping screws
to seal any potential air
leaks
UPFLOW UNIT
 
NOTE - This furnace is not certied for operation in heat-
ing  mode  (indoor  blower  operating  at  selected  heating 
speed) with an external static pressure which exceeds 0.8 
inches  w.c.  Operation  at  these  conditions  may  result  in 
improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a remov-
able access panel should be installed in the supply air 
duct. The access panel should be large enough to per-
mit inspection of the heat exchanger. The furnace access 
panel must always be in place when the furnace is oper-
ating and it must not allow leaks. In horizontal units, in-
stall self tapping screws in the three evaporator coil screw 
the vestibule panel.
Return Air Plenum
NOTE - Return air must not be drawn from a room 
where this furnace, or any other gas-fueled appliance 
(i.e., water heater), or carbon monoxide-producing de-
vice (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure 
is created in the room. If a gas appliance is operating in 
pulled back down the vent pipe and into the room. This 
-
bustion and the formation of carbon monoxide gas. This 
raw gas or toxic fumes might then be distributed through-
out the house by the furnace duct system.
Return air can be brought in through the bottom or either 
side of the furnace (return air brought into either side of 
with bottom return air is installed on a platform, make an 
airtight seal between the bottom of the furnace and the 
platform to ensure that the unit operates properly and 
-
lent sealing method between the plenum and the furnace