Page 4
In order to ensure proper unit operation in non-direct vent 
applications, combustion and ventilation air supply must 
be provided according to the current National Fuel Gas 
Code or CSA-B149 standard.
Installation Locations
clearances to combustible material as listed on the unit 
nameplate and in the table in Figure 12. Accessibility and 
-
tion clearances.
NOTE - For installation on combustible oors, the furnace 
shall  not  be  installed  directly  on  carpeting,  tile,  or  other 
combustible material other than wood ooring.
For installation in a residential garage, the furnace must 
be installed so that the burner(s) and the ignition source 
are located no less than 18 inches (457 mm) above the 
  
physical damage by vehicles. When a furnace is installed 
in a public garage, hangar, or other building that has a 
hazardous atmosphere, the furnace must be installed ac-
cording to recommended good practice requirements and 
current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature 
rise within the range specied on the unit nameplate. Fail-
ure to do so may cause erratic limit operation and prema-
ture heat exchanger failure.
This EL297UHV furnace must be installed so that its elec-
trical components are protected from water. Installed in 
Combination with a Cooling Coil When this furnace is 
used with cooling coils (Figure 3), it shall be installed in 
parallel with, or on the upstream side of, cooling coils to 
avoid condensation in the heating compartment. With a 
     
from entering the furnace. If the damper is manually op-
erated, it must be equipped to prevent operation of either 
the heating or the cooling unit, unless it is in the full HEAT 
or COOL setting.
When installed, this furnace must be electrically grounded 
according to local codes. In addition, in the United States, 
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code 
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit 
must be installed according to the current regulations of 
the Canadian Electrical Code Part I (CSA Standard C22.1) 
and/or local codes.
Gas Unit
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Dampers
(open during heating operation only)
Dampers
(open during cooling operation only)
Heating Unit Installed Parallell to Air Handler Unit
Air Handler Unit
Evaporator
Figure 3 
NOTE - This furnace is designed for a minimum contin-
uous return air temperature of 60°F (16°C) or an inter-
mittent operation down to 55°F (13°C) dry bulb for cases 
where a night setback thermostat is used. Return air tem-
perature must not exceed 85°F (29°C) dry bulb.
The EL297UHV furnace may be installed in alcoves, clos-
ets, attics, basements, garages, crawl spaces and utility 
        
homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Units may be used for heating of buildings or structures 
under construction, if the following conditions are met to 
ensure proper operation:
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT 
UNLESS ALL OF THE FOLLOWING CRITERIA ARE 
MET:
•   
must be permanently installed per these installation in-
structions.
•    Furnace must be installed as a two pipe system and 
one hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion.
•    A room thermostat must control the furnace. The use 
prohibited.
•   The input rate and temperature rise must be set per the 
furnace rating plate. 
•    Supply and Return air ducts must be provided and 
sealed to the furnace. Return air must be terminated 
outside of the space where furnace is installed.
•   Return air temperature range between 60°F (16°C) and 
 80°F (27°C) must be maintained. 
•     
system and must be regularly inspected and maintained 
(e.g., regular static checks and replaced at end of life) 
during construction.