Page 32
Condensate Piping
This unit is designed for either right- or left-side exit of 
      
applications, the condensate trap must extend below the 
unit. An 8” service clearance is required for the conden-
sate trap. Refer to Figure 45 and Figure 47 for condensate 
trap locations. Figure 53 shows trap assembly using 1/2” 
PVC or 3/4” PVC.
NOTE - If necessary the condensate trap may be installed 
up to 5’ away from the furnace. Use PVC pipe to connect 
trap  to  furnace  condensate  outlet.  Piping  from  furnace 
must slope down a minimum of 1/4” per ft. toward trap.
1 -    Determine which side condensate piping will exit 
length of PVC pipe required to reach available 
drain.
2 -         
socket extension and remove plug (Figure 45) from 
the cold end header box at the appropriate location 
on the side of the unit. Install provided 3/4 NPT 
     
NOTE - Cold end header box drain plugs are facto-
ry installed. Check the unused plug for tightness to 
prevent leakage.
3 -   Install the cap over the clean out opening at the 
base of the trap. Secure with clamp. See Figure 53.
4 -        
glue all joints. Glue the provided drain trap as 
shown in Figure 53. Route the condensate line to 
an open drain. Condensate line must maintain a 
1/4” downward slope from the furnace to the drain.
5 -   Figure 48 and Figure 49 show the furnace and 
evaporator coil using a separate drain. If necessary 
the condensate line from the furnace and evaporator 
coil can drain together. See Figure 50, Figure 51 and 
Figure 52. Upow furnace 
      
be a minimum 1” to a maximum 2” length above 
the condensate drain outlet connection. Any length 
        
if the combined primary drain line were to become 
restricted.  Horizontal furnace (Figure 52) - In 
     
vent must be a minimum 4” to a maximum 5” length 
above the condensate drain outlet connection. 
      
exchanger if the combined primary drain line were 
to become restricted.
CONDENSATE TRAP AND PLUG  LOCATIONS
(Unit shown in upflow position)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1-1/2 in.
Rubber
Grommet
Figure 45 
NOTE - In  horizontal  applications  it  is  recommended  to 
install a secondary drain pan underneath the unit and trap 
assembly.
NOTE - Appropriately sized tubing and barbed tting may 
be used for condensate drain. Attach to the drain on the 
trap using a hose clamp. See Figure 46.
Field Provided Drain Components
Tubing
Hose Clamp
Barbed Fitting
Elbow
Figure 46 
 CAUTION
Do not use copper tubing or existing copper condensate 
lines for drain line.