Page 54
NOTE - The o portion of the selected ramp prole also 
applies during  heat pump operation in dual fuel applica-
tions.
TABLE 14 
Cooling Mode Blower Speed Ramping
Ramping Switch 9 Switch 10
A (Factory)  
B  On
C On 
D On On
Ramping Option A (Factory Selection)
•   Motor runs at 50% for 30 seconds.
•    Motor then runs at 82% for approximately 7-1/2 
minutes.
•    -
•    Once demand is met, motor runs at 50% for 30 
seconds then ramps down to stop.
OFF
1/2 MIN
50% CFM
COMPRESSOR DEMAND
7 1/2 MIN
82% CFM
100% 
CFM
1/2 MIN
50% CFM
 
Ramping Option B
•   Motor runs at 82% for approximately 7-1/2 minutes. 
        -
•   Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COMPRESSOR DEMAND
7 1/2 MIN
 
Ramping Option C
•  
•   Once demand is met, motor runs at 100% for 45 
seconds then ramps down to stop.
OFF
100% CFM
100% CFM
45 SEC.
COMPRESSOR
DEMAND
 
Ramping Option D
•  
•  Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COMPRESSOR
 DEMAND
 
Switches 11, 12 and 13 -- Heating Mode Blower Speed  
The switches are factory set to the OFF position which 
provides factory default heat speed. Refer to TABLE 15 
for switches 11, 12 and 13 that provided the correspond-
ing increases or decrease to both high and low heat de-
mand. See TABLE 23 on page 72 for allowable heating 
speeds.
TABLE 15 
Heating Mode Blower Speeds
Heat Speed Switch 11 Switch 12 Switch 13
Increase 24% On On On
Increase 18% On On 
Increase 12% On  On
Increae 6% On   
Factory 
Default
  
Decrease 6%   On
Decrease 
12%
 On 
Decrease 
18%
 On On
Switches 14 and 15 -- Continuous Blower Speed --
TABLE 16 provides continuous blower speed adjustments 
TABLE 16 
Continuous Blower Speed
Coninuous Blower Speed Switch 14 Switch 15
28% of High Cool Speed  On
38% of High Cool Speed
(Factory Setting)
 
Switch 16 - Not Used